Troubleshooting/Service
7.3 Power-up Tests
What happens at power-up
When power is applied, the controller will run three diagnostic tests. After these tests are completed, “TEST DONE” is displayed.
Test Failures
If one or more of these tests fail, the controller will go to the Failsafe Manual Mode, and FAILSF will flash in the lower display and a message indicating which test failed will appear in the lower display. Then, “DONE” will appear in the lower display.
Three Position Step test failures
For controller configured for Three Position Step Control with motor position indication and
7.4Status Tests
Introduction
When required, the results of these tests can be checked to determine the reason the controller has gone to Failsafe.
How to check the status tests
The procedure in Table
Table
Results
Step | Operation |
| Press | Result | |
1 | Select |
|
|
| Upper Display = READ |
| Setup |
| |||
| STATUS |
|
| Lower Display = STATUS | |
|
|
|
| ||
| Set Up Group |
|
|
|
|
|
|
|
|
| |
2 | Read the test |
|
|
| You will see: |
| Function |
| |||
| results |
|
| Upper Display = NO or YES YES indicates a failure | |
|
|
|
|
| |
|
|
|
|
| Lower Display = FAILSAFE |
Function
Upper Display = PASS or FAIL Lower Display = TEST
4/07 | UDC2500 Universal Digital Controller Product Manual | 161 |