Configuration

 

 

 

 

 

 

 

 

 

 

 

 

Function Prompt

Selection or Range of Setting

 

 

Parameter

 

Lower Display

Upper Display

 

 

Definition

 

English

Numeric

English

 

Numeric

 

 

 

 

 

 

 

Code

 

 

Code

 

 

 

 

 

 

FREQ

1203

 

 

 

 

 

POWER LINE FREQUENCY—Select

 

 

 

 

 

 

 

 

whether your controller is operating at 50 or

 

 

 

60

 

0

 

 

60 Hertz.

 

 

 

 

 

 

 

 

 

 

 

 

50

 

1

 

 

ATTENTION

For controllers powered by

 

 

 

 

 

 

 

 

+24 Vdc, this configuration should be set to

 

 

 

 

 

 

 

 

the AC line frequency used to produce the

 

 

 

 

 

 

 

 

+24 Vdc supply.

 

 

 

 

 

 

 

 

Incorrect setting of this parameter may cause

 

 

 

 

 

 

 

 

normal mode noise problems in the input

 

 

 

 

 

 

 

 

readings.

 

DISPLY

1205

 

 

 

 

 

DEFAULT DISPLAY—For single display

 

 

 

 

 

 

 

 

units, only. This setting selects the default

 

 

 

 

 

 

 

 

parameter shown on the upper display.

 

 

 

 

 

 

 

 

Pressing the LOWER DISPLAY key will

 

 

 

 

 

 

 

 

cycle through all applicable values. One

 

 

 

 

 

 

 

 

minute after the last press of the display key,

 

 

 

 

 

 

 

 

the display will revert to the display

 

 

 

 

 

 

 

 

configured here.

 

 

 

SP

0

 

 

SETPOINT—Active Setpoint

 

 

 

PRY

1

 

 

PV-YES—Process Variable with lower

 

 

 

 

 

 

 

 

display prompt.

 

 

 

PRN

2

 

 

PV-NO—Process Variable with no lower

 

 

 

 

 

 

 

 

display prompt.

 

LWRDSP

1204

 

 

 

 

 

LOWER DISPLY—For dual display units,

 

 

 

 

 

 

 

 

only. Select whether the unit uses single or

 

 

 

 

 

 

 

 

dual display.

 

 

 

ENAB

0

 

 

ENAB—Enable Dual Display

 

 

 

DIS

1

 

 

DIS—Disable Dual Display (Single Display

 

 

 

 

 

 

 

 

Only)

 

LNGUAG

1206

 

 

 

 

 

LANGUAGE—This selection designates the

 

 

 

 

 

 

 

 

prompt language.

 

 

 

ENGL

0

 

 

ENGLISH

 

 

 

FREN

1

 

 

FRENCH

 

 

 

GERM

2

 

 

GERMAN

 

 

 

SPAN

3

 

 

SPANISH

 

 

 

ITAL

4

 

 

ITALIAN

 

 

 

NUMB

5

 

 

NUMERIC

 

 

 

 

 

 

 

 

 

 

TCDIAG

1207

 

 

 

 

 

THERMOCOUPLE DIAGNOSTICS—Enable

 

 

 

 

 

 

 

 

or disable Thermocouple diagnostic

 

 

 

 

 

 

 

 

messages.

 

 

 

ENAB

0

 

 

ENAB—Enable Diagnostic Messages

 

 

 

DIS

1

 

 

DIS—Disable Diagnostic Messages

 

 

 

 

 

 

 

 

 

 

 

4/07