Modbus Read, Write and Override Parameters plus Exception Codes

10.7.7Input 2

Table 10-15lists all the register addresses and ranges or selections for the function parameters in Set-up Group Input 2.

 

 

Table 10-15 Set-up Group – Input 2

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

Input 2 Type

00AA

170

INT

R/W

0 = Disable

 

 

 

 

 

1 to 25 Unused

 

 

 

 

 

26

= 0-20 mA

 

 

 

 

 

27

= 4-20 mA

 

 

 

 

 

28 to 30 = Unused

 

 

 

 

 

31

= 0-5 Vdc

 

 

 

 

 

32

= 1-5 Vdc

 

 

 

 

 

33

= Unused

 

 

 

 

 

34

= Unused

 

 

 

 

 

35

= 0 – 2 Vdc

 

 

 

 

 

 

 

ATTENTION

Changing the Input Type will result in the loss of Field Calibration values and will restore the Factory Calibration values.

4/07

UDC2500 Universal Digital Controller Product Manual

207

Page 221
Image 221
Honeywell UDC2500 manual Set-up Group Input