Configuration

 

 

 

 

 

 

 

 

 

Function Prompt

Selection or Range of Setting

 

Parameter

 

Lower Display

Upper Display

 

Definition

 

English

Numeric

English

Numeric

 

 

 

 

 

Code

 

Code

 

 

 

 

 

 

DIS

 

DISABLE – The current SetPoint is used to

 

 

 

 

 

derive a single set of blended tuning

 

 

 

 

 

parameters. This tuning is performed over

 

 

 

 

 

the range of the output limits similar to

 

 

 

 

 

Simplex Tuning. The Tuning Parameters

 

 

 

 

 

derived are placed into both the HEAT and

 

 

 

 

 

COOL tune sets (PID 1 and PID 2).

 

 

 

 

 

 

 

AT ERR

304

 

 

ACCUTUNE ERROR STATUS—When an

 

(Read Only)

 

 

 

error is detected in the Accutune process, an

 

 

 

 

 

error prompt will appear

 

 

 

NONE

0

NONE—No errors occurred during last

 

 

 

 

 

Accutune procedure.

 

 

 

RUN

5

RUNNING—An Accutune process is still

 

 

 

 

 

active checking process gain, even though

 

 

 

 

 

“TUNE” is not lit. It does not affect keyboard

 

 

 

 

 

operation.

 

 

 

ABRT

4

CURRENT ACCUTUNE PROCESS

 

 

 

 

 

ABORTED—Caused by one of the following

 

 

 

 

 

conditions:

 

 

 

 

 

• changing to manual mode

 

 

 

 

 

digital input detected

 

 

 

 

 

in heat region of output but a cool output

 

 

 

 

 

was calculated, or vice versa.

 

 

 

SP2

6

SP2—LSP2 not configured or a Setpoint

 

 

 

 

 

other than LSP1 or LSP2 is in use.

4/07

UDC2500 Universal Digital Controller Product Manual

45

Page 59
Image 59
Honeywell UDC2500 manual At Err, Accutune Error STATUS-When an, Current Accutune Process