Configuration

3.4 Tuning Set Up Group

Introduction

Tuning consists of establishing the appropriate values for the tuning constants you are using so that your controller responds correctly to changes in process variable and setpoint. You can start with predetermined values but you will have to watch the system to see how to modify them. The Accutune feature automatically selects Gain, Rate, and Reset on demand.

ATTENTION

Because this group contains functions that have to do with security and lockout, we recommend that you configure this group last, after all other configuration data has been loaded.

Function Prompts

Table 3-4 TUNING Group (Numeric Code 100) Function Prompts

 

Function Prompt

 

Selection or Range of Setting

 

Parameter

 

Lower Display

 

Upper Display

 

Definition

 

English

Numeric

 

 

English

 

Numeric

 

 

 

 

Code

 

 

 

 

Code

 

 

 

PB or GAIN

101

 

 

PB = 0.1 to 1000 %

 

 

PROPORTIONAL BAND (simplex) is the

 

 

 

 

 

percent of the range of the measured

 

 

 

 

 

Gain = 0.01 to

 

 

variable for which a proportional controller

 

 

 

 

1000

 

 

 

 

 

 

 

 

 

 

will produce a 100 % change in its output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAIN is the ratio of output change (%) over

 

 

 

 

 

 

 

 

 

the measured variable change (%) that

 

 

 

 

 

 

 

 

 

caused it.

 

 

 

 

 

 

 

 

100%

 

 

 

 

 

 

 

 

 

G = PB%

 

 

 

 

 

 

 

 

 

where PB is the proportional band (in %)

 

 

 

 

 

 

 

 

 

If the PB is 20 %, then the Gain is 5. And, at

 

 

 

 

 

 

 

 

 

those settings, a 3 % change in the error

 

 

 

 

 

 

 

 

 

signal (SP-PV) will result in a 15 % change in

 

 

 

 

 

 

 

 

 

the controller's output due to proportional

 

 

 

 

 

 

 

 

 

action. If the Gain is 2, then the PB is 50 %.

 

 

 

 

 

 

 

 

 

Also defined as "HEAT" Gain on Duplex

 

 

 

 

 

 

 

 

 

models for variations of Heat/Cool

 

 

 

 

 

 

 

 

 

applications.

 

 

 

 

 

 

 

 

 

The selection of Proportional Band or Gain is

 

 

 

 

 

 

 

 

 

made in the CONTROL parameter group

 

 

 

 

 

 

 

 

 

under prompt PBorGAIN.

 

 

 

 

 

 

 

 

 

 

 

RATE T

102

 

 

0.00 to 10.00

 

 

RATE action, in minutes, affects the

 

 

 

 

 

controller's output whenever the deviation is

 

 

 

 

 

minutes

 

 

 

 

 

 

 

 

 

changing; and affects it more when the

 

 

 

 

 

0.08 or less = OFF

 

 

 

 

 

 

 

 

 

deviation is changing faster.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

35

Page 49
Image 49
Honeywell UDC2500 manual Tuning Set Up Group, Rate T