Modbus Read, Write and Override Parameters plus Exception Codes
10.7.10Communications
Table
|
| Table | |||||
Parameter | Register | Data | Access |
| Data Range or | ||
Description | Address | Type |
|
| Enumerated Selection | ||
| Hex |
| Decimal |
|
|
|
|
Communication | 004D |
| 77 | FP | R/W | 1 - 99 | |
Address |
|
|
|
|
|
|
|
Communications | 00E7 |
| 231 | INT | R/W | 0 = None | |
Type |
|
|
|
|
| 1 | = Disable |
|
|
|
|
|
| 2 | = |
|
|
|
|
|
| 3 | = Ethernet |
IR Port Enable | 00F1 |
| 241 | INT | R/W | 0 = Disable | |
|
|
|
|
|
| 1 | =- Enable |
Baud Rate | 00E8 |
| 232 | INT | R/W | 0 = 4800 | |
|
|
|
|
|
| 1 | = 9600 |
|
|
|
|
|
| 2 | = 19200 |
|
|
|
|
|
| 3 | = 38400 |
Transmit Delay | 004E |
| 78 | FP | R/W | Response Delay in ms | |
|
|
|
|
|
| (1 to 500) +6ms | |
Floating Point | 00E9 |
| 233 | INT | R/W | 0 = Big Endian | |
Byte Order |
|
|
|
|
| 1 | = Big Endian Byte Swap |
|
|
|
|
|
| 2 | = Little Endian |
|
|
|
|
|
| 3 | = Little Endian Byte Swap |
Shed Enable | 00EA |
| 234 | INT | R/W | 0 = Enable | |
|
|
|
|
|
| 1 | = Disable |
Shed Time | 004F |
| 79 | INT | R/W | 0 = No Shed | |
|
|
|
|
|
| 1 = 255 sample periods | |
|
|
|
|
|
|
| |
Shed Mode and | 00A2 |
| 162 | INT | R/W | 0 = Last Mode and Last Output | |
Output |
|
|
|
|
| 1 | = Manual Mode, Last Output |
|
|
|
|
|
| ||
|
|
|
|
|
| 2 = Manual Mode, Failsafe Output | |
|
|
|
|
|
| 3 | = Automatic Mode |
|
|
|
|
|
|
| |
Shed Setpoint | 00A3 |
| 163 | INT | R/W | 0 = To Last Local Setpoint used | |
Recall |
|
|
|
|
| 1 | = CSP |
Computer | 005A |
| 90 | FP | R/W | ||
Setpoint Ratio |
|
|
|
|
|
|
|
Computer | 005B |
| 91 | FP | R/W | ||
Setpoint Bias |
|
|
|
|
|
|
|
Comm Data | 00A1 |
| 161 | INT | R/W | 0 = Percent | |
Units |
|
|
|
|
| 1 | = Engineering Units |
|
|
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 213 |