Installation
2.4 Control and Alarm Relay Contact Information
Control Relays
ATTENTION
Control relays operate in the standard control mode (that is, energized when output state is on).
Table 2-2 Control Relay Contact Information
Unit Power | Control Relay | Control Relay | Output #1 or #2 |
| Wiring | Contact | Indicator Status |
Off | N.O. | Open | Off |
|
|
| |
| N.C. | Closed | |
|
| ||
|
|
|
|
On | N.O. | Open | Off |
|
|
|
|
|
| Closed | On |
|
|
|
|
| N.C. | Closed | Off |
|
|
|
|
|
| Open | On |
|
|
|
|
Alarm Relays
ATTENTION
Alarm relays are designed to operate in a failsafe mode (that is,
Table 2-3 Alarm Relay Contact Information
| Unit |
|
| Alarm Relay |
| Variable NOT in Alarm State | |||
| Power |
|
| Wiring |
|
|
|
|
|
|
|
|
| Relay |
| Indicators |
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| Contact |
|
|
|
| Off |
| N.O. | Open |
| Off | |||
|
|
|
| N.C. | Closed |
|
|
| |
|
|
|
|
|
|
| |||
| On |
| N.O. | Closed |
| Off | |||
|
|
|
|
|
|
|
|
| |
|
|
|
| N.C. | Open |
|
|
| |
|
|
|
|
|
|
|
|
|
|
Variable in Alarm State
Relay | Indicators |
Contact |
|
Open | Off |
Closed |
|
Open |
|
On | |
Closed |
|
|
|
14 | UDC2500 Universal Digital Controller Product Manual | 4/07 |