Monitoring and Operating the Controller

Step

Operation

 

Press

Result

5

Initiate Tuning

 

 

 

Select “DoSLOW” or “DoFAST” in

 

 

 

 

 

lower display.

6

Tuning in operation

 

 

 

Upper display will flash “TUNE” as

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NoTune” prompt.

 

 

 

 

 

 

Table 4-15 Procedure for Using MANUAL TUNE for Cool side of Duplex Control

Step

Operation

 

Press

Result

1

Configure LSP2

 

 

 

Until 2SP (Local Setpoint 2) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until LSP2 is a value within the

 

 

 

 

 

Cool Zone (output below 50%).

3

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

M-A

 

 

“Automatic” Mode

 

Reset

 

controllers with Manual option).

 

 

 

 

 

4

Show Tuning

 

 

 

Until “NoTUNE” is shown on lower

 

Lower

 

 

Prompt

 

Display

 

display.

 

 

 

 

 

5

Initiate Tuning

 

 

 

Select “DoSLOW” or “DoFAST” in

 

 

 

 

 

lower display.

6

Tuning in operation

 

 

 

Upper display will flash “TUNE” as

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NoTune” prompt.

108

UDC2500 Universal Digital Controller Product Manual

4/07

Page 122
Image 122
Honeywell UDC2500 manual 108