Monitoring and Operating the Controller
Set up Procedure
Use the following procedure (Table
•select two sets,
•set the
•set tuning constant value for each set.
Table 4-18 Set Up Procedure
Step
Operation
Press
Result
1Select Control
2Select PID SETS
Setup
Function
Until you see:
Upper Display = SET
Lower Display = CONTRL
Until you see:
Upper Display = (available selections) Lower Display = PID SETS
3 | Select PID SETS | or To select the type of function. Available selections are: |
| Function |
2
2
2
4 | Set Tuning | Function |
| Values for Each | |
|
| |
| Set |
|
5 | Set Switchover | Function |
| Value for 2PR or | |
|
| |
| 2SP Selection |
|
|
| or |
Refer to “TUNING” Set up group, subsection 3.4 and set the following tuning parameters:
PB or GAIN*
RATE T*
I MIN or I RPM*
CYCT1 or CTIX3*
PB2 or GAIN2**
RATE 2T**
I2MIN or I2RPM**
CYC2T2 or CT2X3**
*PIDSET1 will be used when PV or SP, whichever is selected, is greater than the switchover value.
**PIDSET2 will be used when PV or SP, whichever is selected, is less than the switchover value.
Until you see:
Upper Display = (the switchover value)
Lower Display = SW VAL
To select the switchover value in the upper display.