Modbus Read, Write and Override Parameters plus Exception Codes

Parameter

Register

Data

Access

 

Data Range or

Description

Address

Type

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

Alarm 1 Setpoint 2

008E

142

INT

R/W

Same as 140

Type

 

 

 

 

 

 

 

 

 

 

 

 

Alarm 2 Setpoint 1

0090

144

INT

R/W

Same as 140

Type

 

 

 

 

 

 

 

 

 

 

 

 

Alarm 2 Setpoint 2

0092

146

INT

R/W

Same as 140

Type

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm 1 Setpoint 1

008D

141

INT

R/W

0

= Low Alarm

Event

 

 

 

 

1

= High Alarm

 

 

 

 

 

 

 

Alarm 1 Setpoint 2

008F

143

INT

R/W

0

= Low Alarm

Event

 

 

 

 

1

= High Alarm

 

 

 

 

 

 

 

Alarm 2 Setpoint 1

0091

145

INT

R/W

0

= Low Alarm

Event

 

 

 

 

1

= High Alarm

 

 

 

 

 

 

 

Alarm 2 Setpoint 2

0093

147

INT

R/W

0

= Low Alarm

Event

 

 

 

 

1

= High Alarm

 

 

 

 

 

 

Alarm Hysteresis

0029

041

FP

R/W

0.0 to 100% of output or

 

 

 

 

 

span

 

 

 

 

 

 

 

Alarm Latching for

00C8

200

INT

R/W

0

= Non Latching

Output 1

 

 

 

 

1

= Latching

 

 

 

 

 

 

Alarm States

00C9

201

INT

R/W

State = 0 = Not in Alarm

 

 

 

 

 

State = 1 = In Alarm

 

 

 

 

 

 

Bit 0 = Alarm 11 State

 

 

 

 

 

 

Bit 1 = Alarm 12 State

 

 

 

 

 

 

Bit 2 = Alarm 21 State

 

 

 

 

 

 

Bit 3 = Alarm 22 State

 

 

 

 

 

Event = 0 = Low

 

 

 

 

 

Event = 1 = High

 

 

 

 

 

 

Bit 4 = Alarm 11 Event

 

 

 

 

 

 

Bit 5 = Alarm 12 Event

 

 

 

 

 

 

Bit 6 = Alarm 21 Event

 

 

 

 

 

 

Bit 7 = Alarm 22 Event

 

 

 

 

 

 

 

Alarm 1 Blocking

00CA

202

INT

R/W

0

= Disable

 

 

 

 

 

1

= Block 1

 

 

 

 

 

2

= Block 2

 

 

 

 

 

3

= Block 1 2

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

215

Page 229
Image 229
Honeywell UDC2500 manual Alarm 1 Setpoint 008E 142