Modbus Read, Write and Override Parameters plus Exception Codes

10.7.11Alarms

Table 10-19lists all the register addresses and ranges or selections for the function parameters in Set-up Group Alarms.

 

 

Table 10-19 Set-up Group – Alarms

Parameter

Register

Data

Access

 

 

 

Data Range or

Description

Address

Type

 

 

 

Enumerated Selection

 

Hex

Decimal

 

 

 

 

 

 

Alarm 1 Setpoint 1

0009

009

FP

R/W

 

Within the range of

Value

 

 

 

 

selected parameter or PV

 

 

 

 

 

span for deviation alarm

Alarm 1 Setpoint 2

000A

010

FP

R/W

 

Within the range of

Value

 

 

 

 

selected parameter or PV

 

 

 

 

 

span for deviation alarm

Alarm 2 Setpoint 1

000B

011

FP

R/W

 

Within the range of

Value

 

 

 

 

selected parameter or PV

 

 

 

 

 

span for deviation alarm

Alarm 2 Setpoint 2

000C

012

FP

R/W

 

Within the range of

Value

 

 

 

 

selected parameter or PV

 

 

 

 

 

span for deviation alarm

 

 

 

 

 

 

 

Alarm 1 Setpoint 1

008C

140

INT

R/W

 

0 = None

Type

 

 

 

 

1

= Input 1

 

 

 

 

 

2

= Input 2

 

 

 

 

 

3

= PV

 

 

 

 

 

4

= Deviation

 

 

 

 

 

5

= Output

 

 

 

 

 

6

= Alarm on Shed

 

 

 

 

 

7

= SP Event On

 

 

 

 

 

8

= SP Event Off

 

 

 

 

 

9

= Manual

 

 

 

 

 

10

= Remote Setpoint

 

 

 

 

 

11

= Failsafe

 

 

 

 

 

12

= PV Rate of Change

 

 

 

 

 

13

= Alarm on Digital

 

 

 

 

 

 

 

 

Input 1

 

 

 

 

 

14

= Alarm on Digital

 

 

 

 

 

 

 

 

Input 2

 

 

 

 

 

15

= Loop Break

 

 

 

 

 

16

= Deviation based upon

 

 

 

 

 

 

 

 

SP2

 

 

 

 

 

17

= T/C Warning

 

 

 

 

 

18

= T/C Fail

214

UDC2500 Universal Digital Controller Product Manual

4/07

Page 228
Image 228
Honeywell UDC2500 manual Set-up Group Alarms