Troubleshooting/Service

Procedure #1

Table 7-5explains how to troubleshoot power failure symptoms.

Table 7-5 Troubleshooting Power Failure Symptoms

Step

What to do

How to do it

1

Check the AC line voltage.

Use a voltmeter to measure the AC voltage

 

 

across terminals L1 and L2 on the rear

 

 

terminal panel of the controller.

 

 

Check the earth ground connection.

2

Make sure the chassis plugs

Withdraw the chassis and visually inspect the

 

into the rear of the case

controller board and the inside of the case.

 

properly.

 

3

Check the system for Brown-

Refer to Section 2 - Installation.

 

outs, heavy load switching, etc.,

 

 

and conformance to installation

 

 

instructions.

 

4

Change Power board.

Installation instructions supplied with new

 

 

board.

 

 

 

Procedure #2

Table 7-6explains how to troubleshoot Current Output failure symptoms.

Table 7-6 Troubleshooting Current Output Failure

Step

What to do

How to do it

1

Make sure the controller is

Make Output Set Up group function prompt

 

configured for Current output

OUT ALG = CUR.

 

and the proper range (4 to 20 or

Make the Output Set UP group function

 

0 to 20) is configured.

 

prompt CRANGE = 4–20 or 0–20 per your

 

 

 

 

application.

 

 

Refer to Section 3 - Configuration.

2

Check the field wiring.

Output impedance must be less than or equal

 

 

to 1000 ohms.

3

Check the output.

Put the controller into Manual mode and

 

 

change the output from 0 % to 100 % (4-20

 

 

mA). Use a DC milliammeter at the rear

 

 

terminals to verify the output.

4

Recalibrate the Current

Refer to Section 6 - Output Calibration for

 

Proportional output.

details.

5

Change Current Output board.

Installation instructions provided with new

 

 

board.

6Change Controller

166

UDC2500 Universal Digital Controller Product Manual

4/07

Page 180
Image 180
Honeywell UDC2500 manual Procedure #1, Troubleshooting Power Failure Symptoms, Procedure #2, Step What to do How to do it