Input Calibration

Radiamatic, Millivolts, Volts or Thermocouple Differential Inputs

Refer to Figure 5-5and wire the controller according to the procedure given in Table 5-7.

Table 5-7 Set Up Wiring Procedure for Radiamatic, Millivolts, Volts or

Thermocouple Differential Inputs (Except 0-10 Volts)

Step

Action

 

 

1Connect the copper leads from the calibrator to the Input #1 terminals as shown in Figure 5-5.

2Place current/voltage source at zero before switching on.

3Do not switch current/voltage source ON/OFF while connected to the instrument.

ATTENTION

For Radiamatic inputs only, set Emissivity value to 1.0. See Subsection 3.9 Configuration Set Up prompt INPUT1, function prompt EMISS.

Millivolt or

+

Volt Source

_

 

 

26+

27-

Figure 5-5 Wiring Connections for Radiamatic, Thermocouple Differential,

Millivolts or Volts (Except 0 to 10 Volts)

142

UDC2500 Universal Digital Controller Product Manual

4/07

Page 156
Image 156
Honeywell UDC2500 manual Millivolt or Volt Source 26+