Configuration

 

Function Prompt

 

Selection or Range of Setting

 

 

Parameter

 

Lower Display

 

Upper Display

 

 

Definition

 

English

Numeric

 

 

English

Numeric

 

 

 

 

 

 

Code

 

 

 

Code

 

 

 

 

 

XMITR1

602

 

 

B

0

 

 

TRANSMITTER CHARACTERIZATION

 

 

 

 

 

 

 

This selection lets you instruct the controller

 

 

 

 

 

E H

1

 

 

 

 

 

 

 

 

 

to characterize a linear input to represent a

 

 

 

 

 

E L

2

 

 

 

 

 

 

 

 

 

non-linear one. If characterization is

 

 

 

 

 

J H

3

 

 

 

 

 

 

 

 

 

performed by the transmitter itself, then

 

 

 

 

 

J M

4

 

 

 

 

 

 

 

 

 

select LIN (Linear).

 

 

 

 

 

J L

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K H

6

 

 

ATTENTION

Prompt only appears when a

 

 

 

 

 

K M

7

 

 

linear actuation

is selected at prompt IN1

 

 

 

 

 

K L

8

 

 

TYPE.

 

 

 

 

 

NNMH

9

 

 

FOR EXAMPLE:

 

 

 

 

 

NNML

10

 

 

 

 

 

 

 

NICH

11

 

 

If input 1 is a 4 to 20 mA signal, but the

 

 

 

 

 

NICL

12

 

 

signal represents a type K H thermocouple,

 

 

 

 

 

R

13

 

 

then configure K H and the controller will

 

 

 

 

 

S

14

 

 

characterize the 4 to 20 mA signal so that it

 

 

 

 

 

T H

15

 

 

is treated as a type K thermocouple input

 

 

 

 

 

T L

16

 

 

(high range).

 

 

 

 

 

W H

17

 

 

Parameter definitions are the same as in IN1

 

 

 

 

 

W L

18

 

 

 

 

 

 

 

 

 

TYPE.

 

 

 

 

 

100H

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100L

20

 

 

 

 

 

 

 

 

200

21

 

 

 

 

 

 

 

 

500

22

 

 

 

 

 

 

 

 

 

RADH

23

 

 

 

 

 

 

 

 

 

RADI

24

 

 

 

 

 

 

 

 

 

LIN

25

 

 

 

 

 

 

 

 

 

SrT

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN1 HI

603

 

 

999 to 9999

 

 

 

INPUT 1 HIGH RANGE VALUE in

 

 

 

 

 

 

engineering units is displayed for all inputs

 

 

 

 

 

floating in

 

 

 

 

 

 

 

 

 

 

 

but can only be configured for linear or

 

 

 

 

 

engineering units

 

 

 

 

 

 

 

 

 

 

 

square root transmitter characterization.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Scale the #1 input signal to the display value

 

 

 

 

 

 

 

 

 

you want for 100 %.

 

 

 

 

 

 

 

 

 

EXAMPLE:

 

 

 

 

 

 

 

 

 

Process Variable = Flow

 

 

 

 

 

 

 

 

 

Range of Flow = 0 to 250 Liters/Minute

 

 

 

 

 

 

 

 

 

Actuation (Input 1) = 4 to 20 mA

 

 

 

 

 

 

 

 

 

Characterization (XMITTER) = LINEAR

 

 

 

 

 

 

 

 

 

Set IN1 HI display value to 250

 

 

 

 

 

 

 

 

 

Set IN1 LO display value to 0

 

 

 

 

 

 

 

 

 

Then 20 mA = 250 Liters/Minute

 

 

 

 

 

 

 

 

 

and 4 mA = 0 Liters/Minute

 

 

 

 

 

 

 

 

 

 

The control setpoint will be

 

 

 

 

 

 

 

 

 

ATTENTION

 

 

 

 

 

 

 

 

 

limited by the

range of units selected here.

 

 

 

 

 

 

 

 

 

 

 

56

UDC2500 Universal Digital Controller Product Manual

4/07

Page 70
Image 70