This selection results in performance tuning over the full range utilizing both Heat and Cool outputs to acquire blended tune values that are then applied to both Heat and Cool tuning parameters. Both PID sets are set to the same values.
Table
Step | Operation |
| Press | Result | |
1 | Configure LSP1 |
|
|
| Until SP (Local Setpoint 1) shows |
| Lower |
| |||
|
|
| Display |
| in the lower display. |
|
|
|
|
| |
2 |
|
| or |
| Until the Setpoint is to the desired |
|
|
|
|
| value. |
3 | Switch to |
|
|
| Until the “A” indicator is lighted (on |
|
| ||||
| “Automatic” Mode |
| Reset |
| controllers with Manual option). |
|
|
|
|
| |
4 | Show Tuning |
|
|
| Until “NoTUNE” is shown on lower |
| Lower |
| |||
| Prompt |
| Display |
| display. |
|
|
|
|
| |
5 | Initiate Tuning |
|
|
| Select “DoSLOW” or “DoFAST” in |
|
|
|
|
| lower display. |
6 | Tuning in operation |
|
|
| Upper display will flash “TUNE” as |
| Lower |
| |||
|
|
| Display |
| long as ACCUTUNE process is |
|
|
|
|
| operating. When process |
|
|
|
|
| completes, tuning parameters are |
|
|
|
|
| calculated and lower display will |
|
|
|
|
| show “NoTune” prompt. |
4.11.5Using MANUAL TUNE at start-up for Duplex (Heat/Cool)
When DUPLEX has been configured for MANUAL. This selection should be used when tuning is needed only for the HEAT zone or only for the COOL zone but not both. If Local Setpoint 1 is used, then the controller will perform a HEAT zone tune. If Local Setpoint 2 is used, then the controller will perform a COOL zone tune.
Table
Step | Operation |
| Press | Result | |
1 | Configure LSP1 |
|
|
| Until SP (Local Setpoint 1) shows |
| Lower |
| |||
|
|
| Display |
| in the lower display. |
|
|
|
|
| |
2 |
|
| or |
| Until LSP1 is a value within the |
|
|
|
|
| Heat Zone (output above 50%). |
3 | Switch to |
|
|
| Until the “A” indicator is lighted (on |
|
| ||||
| “Automatic” Mode |
| Reset |
| controllers with Manual option). |
|
|
|
|
| |
4 | Show Tuning |
|
|
| Until “NoTUNE” is shown on lower |
| Lower |
| |||
| Prompt |
| Display |
| display. |
|
|
|
|
| |
|
|
|
|
|
|
4/07 | UDC2500 Universal Digital Controller Product Manual | 107 |