Monitoring and Operating the Controller

This selection results in performance tuning over the full range utilizing both Heat and Cool outputs to acquire blended tune values that are then applied to both Heat and Cool tuning parameters. Both PID sets are set to the same values.

Table 4-13 Procedure for Using BLENDED TUNE at Start-up for Duplex Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until the Setpoint is to the desired

 

 

 

 

 

value.

3

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

M-A

 

 

“Automatic” Mode

 

Reset

 

controllers with Manual option).

 

 

 

 

 

4

Show Tuning

 

 

 

Until “NoTUNE” is shown on lower

 

Lower

 

 

Prompt

 

Display

 

display.

 

 

 

 

 

5

Initiate Tuning

 

 

 

Select “DoSLOW” or “DoFAST” in

 

 

 

 

 

lower display.

6

Tuning in operation

 

 

 

Upper display will flash “TUNE” as

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NoTune” prompt.

4.11.5Using MANUAL TUNE at start-up for Duplex (Heat/Cool)

When DUPLEX has been configured for MANUAL. This selection should be used when tuning is needed only for the HEAT zone or only for the COOL zone but not both. If Local Setpoint 1 is used, then the controller will perform a HEAT zone tune. If Local Setpoint 2 is used, then the controller will perform a COOL zone tune.

Table 4-14 Procedure for Using MANUAL TUNE for Heat side of Duplex Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until LSP1 is a value within the

 

 

 

 

 

Heat Zone (output above 50%).

3

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

M-A

 

 

“Automatic” Mode

 

Reset

 

controllers with Manual option).

 

 

 

 

 

4

Show Tuning

 

 

 

Until “NoTUNE” is shown on lower

 

Lower

 

 

Prompt

 

Display

 

display.

 

 

 

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

107

Page 121
Image 121
Honeywell UDC2500 manual Using Manual Tune at start-up for Duplex Heat/Cool