Monitoring and Operating the Controller
Switch between two sets via keyboard (without automatic
Step
Operation
Press
Result
1Select Control
Function
Until you see:
Upper Display = (the PV value) Lower Display = PIDS X (X= 1 or 2)
2
3
or | To change PID SET 1 to PID SET2 or Vice Versa. | |
You can use Accutune on each set. | ||
| ||
| To accept changes. | |
Function | ||
| ||
|
| |
|
|
4.14 Alarm Setpoints
Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm relay is
The alarm relay is energized when the monitored value goes into the allowed region by more than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or normally closed (NC)
There are four alarm setpoints, two for each alarm. The type and state (High or Low) is selected during configuration. See Subsection 3.13 – Configuration for details.
Alarm Setpoints Display
Table
Step
Operation
Press
Result
1Select Alarm
2Access the Alarm
Setpoint Values
Setup
Function
Until you see:
Upper Display = SET
Lower Display = ALARMS
To successively display the alarm setpoints and their values. Their order of appearance is shown below.
Upper Display = (the alarm setpoint value) Range values are within the range of the selected parameters except:
DEVIATION (DE) value = PV Span
EVENTS
LOOP BREAK ALARMS (BRAK) = The timer value may be changed only for controllers configured for ON/OF.
112 | UDC2500 Universal Digital Controller Product Manual | 4/07 |