Modbus Read, Write and Override Parameters plus Exception Codes

Parameter

Register

Data

Access

 

 

Data Range or

Description

Address

Type

 

 

 

Enumerated Selection

 

 

 

 

 

 

 

 

 

Hex

Decimal

 

 

 

 

 

 

 

 

 

 

 

 

 

Input 1

00A9

169

INT

R/W

0 = B TC

Transmitter

 

 

 

 

1

= E TC H

Characterization

 

 

 

 

2

= E TC L

 

 

 

 

 

3

= J TC H

 

 

 

 

 

4

= J TC M

 

 

 

 

 

5

= J TC L

 

 

 

 

 

6

= K TC H

 

 

 

 

 

7

= K TC M

 

 

 

 

 

8

= K TC L

 

 

 

 

 

9

= NNM H

 

 

 

 

 

10

= NNM L

 

 

 

 

 

11

= Nicrosil H TC

 

 

 

 

 

12

= Nicrosil L TC

 

 

 

 

 

13

= R TC

 

 

 

 

 

14

= S TC

 

 

 

 

 

15

= T TC H

 

 

 

 

 

16

= T TC L

 

 

 

 

 

17

= W TC H

 

 

 

 

 

18

= W TC L

 

 

 

 

 

19

= 100 PT RTD

 

 

 

 

 

20

= 100 PT LO RTD

 

 

 

 

 

21

= 200 PT RTD

 

 

 

 

 

22

= 500 PT RTD

 

 

 

 

 

23

= Radiamatic RH

 

 

 

 

 

24

= Radiamatic RI

 

 

 

 

 

25

= Linear

 

 

 

 

 

26

= Square Root

 

 

 

 

 

 

Input 1 High

001D

029

FP

R/W

–999. to 9999. Engineering

Range Value

 

 

 

 

Units (Linear types only)

 

 

 

 

 

 

Input 1 Low

001E

030

FP

R/W

–999 to 9999. Engineering

Range Value

 

 

 

 

Units (Linear types only)

 

 

 

 

 

 

Input 1 Ratio

006A

106

FP

R/W

–20.00 to 20.00

 

 

 

 

 

 

Input 1 Bias

006B

107

FP

R/W

–999 to 9999. Engineering

 

 

 

 

 

Units

 

 

 

 

 

 

Input 1 Filter

002A

042

FP

R/W

0 to 120 seconds

 

 

 

 

 

 

 

 

4/07

UDC2500 Universal Digital Controller Product Manual

205

Page 219
Image 219