NOTE: While a drain connection is required in the vent of all Cat. III horizontal MVB installations, the drain can be accomplished in several different ways. The figures in this manual show the drain in a vent tee, however, this can also be accomplished using an inline collector for condensing stacks or an inline vertical or horizontal collector available from several of the listed vent manufacturers.
Fig. 27: Horizontal
CAUTION: This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer’s instructions. Failure to install a condensate drain in the venting system will void all warranties on this heater.
Installation
These installations utilize the
The total length of the horizontal
28
•75’ of straight flue pipe
•65’ of straight flue pipe and one elbow
•55’ of straight flue pipe and two elbows
•45’ of straight pipe and three elbows
The vent cap is not considered in the overall length of the venting system.
The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is required that:
1.The vent must be installed with a condensate drain located in proximity to the heater as directed by the vent manufacturer.
2.The vent must be installed with a slight upward slope of not less than 1/4 inch per foot of horizon- tal run to the vent terminal.
3.The vent must be insulated through the length of the horizontal run.
Termination
The flue direct vent cap MUST be mounted on the ex- terior of the building. The direct vent cap cannot be installed in a well or below grade. The direct vent cap must be installed at least 1 ft above ground level and above normal snow levels. The
WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
Direct Vent—Vertical
Installation
These installations utilize the
The connection from the appliance flue to the stack must be as direct as possible and should be the same size or larger than the vent outlet.