TROUBLESHOOTING
Step 1
Step 2
Step 3
Does the power switch provide |
|
|
| NO |
|
|
| Check the switch and/or |
|
|
| |||||||||||||
power to the control panel? |
|
|
|
|
|
|
| line voltage |
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
| Is there a Call For |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| YES |
|
| NO | Unit is in standby mode. |
| |||||||||||||||||
|
|
|
|
|
|
| Heat? |
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Is Disable connection intact? |
| NO |
|
|
| Reattach. |
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check and correct power |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Does the combustion air |
|
|
|
|
|
|
| Is there 120VAC at the blower or |
|
|
| connections at main terminal | ||||||||||||
|
|
| NO |
|
| NO |
| |||||||||||||||||
|
|
|
|
|
|
|
| blower relay? |
|
| block, circuit breaker panel or | |||||||||||||
blower come on? |
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| blower relay. | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Step 4
Is
|
| YES |
YES |
| |
|
| |
|
|
|
Does F2 on ignition module
have AC power?
Is 24VAC at the NC side of | NO | ||
the air pressure switch? | |||
| |||
| |||
|
| ||
YES |
|
| |
|
|
|
| Is diagnostic board |
|
|
|
|
| ||||
|
|
|
|
| NO | |||||
NO |
|
|
|
| ||||||
indicating open |
|
|
|
| ||||||
|
| safeties? |
|
|
|
|
| |||
|
|
|
|
|
|
| ||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||
|
|
|
|
| YES |
|
|
| ||
|
|
|
|
| ||||||
| Is there continuity in the wire | |||||||||
NO | ||||||||||
between F2 and Pin |
| |||||||||
|
| |||||||||
Is blower pressure setting |
|
|
|
|
| |||||
NO |
|
| ||||||||
(vacuum) correct? |
|
| ||||||||
|
|
|
|
| ||||||
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||
|
| YES |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
Replace temperature
controller.
Correct Safety
NO | Repair or |
| Replace wire. |
|
Correct the shutter
setting or blower
amp draw.
Step 5
Step 6
Is 24VAC at PS on ignition module?
Is connecting plug secure?
YES
Does igniter prove? | NO |
|
|
YES
Replace air pressure switch.
NO | Correct wiring. |
|
|
Is Amp draw during heat-
up for HSI greater than NOReplace HSI 3.1 Amps?
YES | Is air switch bouncing? | NO |
|
YES
Step 7
Step 8
| Is the flame sensor signal to the |
| NO |
|
| Is gas pressure correct? |
|
|
| ||||||
|
|
|
|
| NO |
| |||||||||
ignition module greater than 1 uA DC? |
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| YES |
|
|
|
|
|
| |
| YES |
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Is static and dynamic inlet gas |
|
| Correct the gas pressure. | ||||||||||
|
|
|
|
| |||||||||||
|
|
|
|
| |||||||||||
Is the unit running? | NO | ||||||||||||||
| pressure |
| correct? | ||||||||||||
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Step 9
YESNO
The unit is okay
YES
Call our Technical Service Department