OPERATION

for operation as outlined by manufacturer. Burner should be operating and should go off when con- trols are tested. When safety devices are restored, burners should re-ignite after pre-purge time delay.

8.Test limit control: While burner is operating, move indicator on high limit control below actual water temperature. Burner should go off while blower and circulator continue to operate. Raise setting on limit control above water temperature and burner should re-ignite after pre-purge time delay.

NOTE: Ignition control may have to be reset after this portion of the test.

9.Test ignition system safety device:

a.Open manual gas valve. Turn power on.

b.Set thermostat to call for heat.

c.When the heater is in operation, pull hose off the air switch. The burner should go off almost immediately.

d.Reattach hoses. Burner should re-ignite after pre-purge time delay. NOTE: Ignition control may have to be reset after this portion of the test.

10.To restart system, follow lighting instructions in the Operation section.

11.Check to see that the high limit control is set above the design temperature requirements of the system. For multiple zones: Check to make sure the flow is adjusted as required in each zone.

12.Check that the heater is cycled with the thermo- stat. Raise the setting on the thermostat to the highest setting and verify that the heater goes through the normal start-up cycle. Reduce to the lowest setting and verify that the heater goes off.

13.Observe several operating cycles for proper oper- ation.

14.Set the heater thermostat to desired temperature.

15.Review all instructions shipped with this heater with owner or maintenance person, return to enve- lope and give to owner or place the instructions inside front panel on heater.

OPERATION

Lighting Instructions

1.Before operation, make sure you have read all of the safety information in this manual.

2.Remove upper front panel.

3.Set the thermostat to the lowest setting.

4.Turn off all electrical power to the appliance.

5.This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

6.Turn on main manual gas valve field installed near gas inlet connection on back of heater.

7.Wait 5 minutes to clear out any gas. Then smell for gas, especially near the floor. If you then smell gas, STOP! Follow the steps in the safety informa- tion on the front cover of this manual. If you do not smell gas, go to next step.

8.Turn on all electrical power to the appliance.

9.Set thermostat to desired setting. The appliance will operate. The igniter will glow after the pre- purge time delay (15 seconds). After igniter reaches temperature (30 seconds) the main valve should open. System will try for ignition up to three times (one time on optional single-try ignition mod- ule). If flame is not sensed, lockout will commence.

10.If the appliance will not operate, follow the instruc- tions “To Turn Off Gas ToAppliance,” and call your service technician or gas supplier.

11.Replace upper front panel.

12.If heater fails to start, verify the following:

a.There are no loose connections or that the service switch is off.

b.High temperature limit switch is set above wa- ter temperature or manual reset high limit is not tripped.

c.Thermostat is set above water temperature.