| with the blower suction within the tolerances spec- |
| CAUTION: Special manifold and air settings may |
| ||||||||
|
|
| ||||||||||
| ified in Table T, contact the factory. The reference |
| be required. |
| ||||||||
| amp draw reading may help to indicate if there is |
|
| |||||||||
| a problem with the system or if blower adjustment |
| Finishing | |||||||||
| is required. |
|
|
|
|
|
|
|
| |||
| NOTE: Most commercially available amp probes |
|
| 1. | Record all data on the | |||||||
|
|
| ||||||||||
| are not accurate enough and/or are not shielded well |
|
|
|
| at the back of this manual. | ||||||
| enough to read accurately in the heater |
|
| 2. | Disconnect the manometers and reconnect the | |||||||
| environment. Blower amp draw readings are for |
|
| |||||||||
| reference only. |
|
|
|
|
|
|
|
|
| cap on the fan pressure switch tee and reinsert the | |
|
|
|
|
|
|
|
|
|
|
| sealing screws into the bleedle valves. | |
Manifold Check |
|
|
|
|
|
|
| |||||
|
|
|
|
| 3. | |||||||
1. Check manifold gas pressure at the gas valve out- |
|
| operating properly. | |||||||||
| Safety Inspection | |||||||||||
| let pressure tap (connection “D” in Fig. 48). This |
| ||||||||||
| pressure should read per the values in Table X for | 1. | Check all thermostats and high limit settings. | |||||||||
| natural and propane gas. |
|
|
|
|
| ||||||
2. If the pressure reading differs by more than ± 0.2 | 2. | During the following safety checks leave manome- | ||||||||||
| in. WC, STOP – Call the factory for directions |
|
| ters hooked up, check and record. | ||||||||
| on what to do next! |
|
|
|
|
| 3. | If other | ||||
| Model No. |
| Air Pressure |
| Setting |
|
|
| same gas main, check all pressures on the MVB | |||
|
|
|
|
|
| |||||||
|
| Setting (in. WC) |
| Tolerance |
|
|
| with all other equipment running. | ||||
| 504 |
|
| ± 0.2 in. WC |
| 4. | Check thermostats for | |||||
| 754 |
|
| ± 0.2 in. WC |
| |||||||
| 1104 |
|
| ± 0.2 in. WC |
| 5. | Check high limits for | |||||
| 1504 |
|
| ± 0.2 in. WC |
| 6. | While in operation, check flow switch operation. | |||||
| 2004 |
|
| ± 0.2 in. WC |
| |||||||
|
|
|
|
|
|
|
|
| 7. | Check the low gas pressure switch (if provided). | ||
| Table V: |
| MVB Air Pressure |
| Settings |
| ||||||
|
|
|
|
| Setting |
|
|
|
|
| (For proper adjustment, use the attached | |
| Model No. |
| Amp Draw |
|
|
|
|
|
| manometers, if available, to set pressure. The | ||
|
|
| Tolerance |
|
|
|
|
| scales on the switch are approximate only.) Low | |||
| 504 | 1.9 |
|
|
|
|
| |||||
|
|
|
|
|
| gas pressure switch (if provided) must be set at | ||||||
| 754 | 2.9 |
|
|
|
|
| 3.0 in. WC for natural gas and propane gas. | ||||
| 1104 | 5.5 |
|
|
| 8. | Make sure that the high gas pressure switch (op- | |||||
| 1504 | 8.1 |
|
|
| |||||||
| 2004 | 13.0 |
|
|
|
|
| tional) is set to 3.0 in. WC for both natural gas and | ||||
|
|
|
|
|
|
|
|
|
|
| propane gas. | |
| Table W: MVB Amp Draw (Reference Only) |
|
| |||||||||
|
| |||||||||||
|
|
| Manifold Gas Pressure Setting |
|
| |||||||
|
|
|
| |||||||||
| Model No. |
| High Fire Values (in. WC) |
|
| Safety checks must be recorded as performed. | ||||||
|
|
| Natural Gas |
| Propane Gas |
|
| Turn heater on. After main burner ignition: | ||||
| 504 |
|
|
|
|
| 1. | Check manometer for proper readings. | ||||
| 754 |
|
|
|
|
| ||||||
| 1104 |
|
|
|
|
| 2. | Cycle heater several times and | ||||
| 1504 |
|
|
|
|
| 3. | Remove all manometers and replace caps and | ||||
| 2004 |
|
|
|
|
|
|
| screws. | |||
| Table X: MVB Manifold Pressure Settings | 4. | Check for gas leaks one more time. | |||||||||
|
|
|
| 44 | ||||||||
|
|
|
|
|
|
|
|