Raypak 5042004 operating instructions 0-10VDC, 0-20mA, Boiler Target

Models: 5042004

1 56
Download 56 pages 50.66 Kb
Page 32
Image 32
0-10 VDC

ELECTRONIC

trol operates the boiler burner to maintain the boiler target at the boiler outlet sensor.

Mode 7 – Designed for an external input signal with primary/secondary piping. The external input signal can be provided from a BMS, an EMS or an external control. The external input signal changes the boiler target according to a linear scale (see Tables O & P). The control operates the boiler burner to maintain the boiler target at the system sensor. See Fig. 35.

Fig. 33: Mode 3 Dedicated DHW

Mode 4 (Not supported) – Outdoor reset using pri- mary piping. The heater is operated as in Mode 1. However, the target temperature is based on outdoor reset.

Mode 5 – Outdoor reset using primary/secondary pip- ing. The heater is operated as in Mode 2. However, the target temperature is based on outdoor reset. See Fig. 34.

*Maximum 4 times the pipe diameter* or 12”,0-20 mA* whichever is less.

Fig. 34: Mode 5 Primary/Secondary Piping with

Outdoor Reset

Mode 6 (Not supported) – Designed for an external input signal with primary piping. The external input sig- nal can be provided from a BMS, an EMS or a sequencing control. The external input signal changes the boiler target according to a linear scale. The con-

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Maximum 4 times the pipe diameter or 12”, whichever is less.

Fig. 35: Mode 7 Primary/Secondary Piping with

 

External Target Temp

 

 

 

 

 

 

 

 

 

 

 

0-10 VDC

 

 

0-20 mA*

Boiler Target

0

0

 

 

--- (OFF)

1

2

 

 

 

50°F

2

4

 

 

68.9°F

3

6

 

 

87.8°F

4

8

 

 

106.7°F

5

10

 

 

125.6°F

6

12

 

 

144.1°F

7

14

 

 

163.3°F

8

16

 

 

182.2°F

9

18

 

 

201.1°F

10

20

 

 

220°F

*Requires a 500Ω resistor.

Table O: 0-10 VDC or 0-20 mA External Input Signal

32

Page 32
Image 32
Raypak 5042004 operating instructions 0-10VDC, 0-20mA, Boiler Target