Raypak 5042004 Electrical Power Connections, Model, 1 in. NPT, 1-1/4in. NPT, 1-1/2in. NPT

Models: 5042004

1 56
Download 56 pages 50.66 Kb
Page 20
Image 20
1 in. NPT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

1 in. NPT

 

1-1/4 in. NPT

 

1-1/2 in. NPT

 

2 in. NPT

 

 

2-1/2 in. NPT

 

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

P

 

N

P

 

N

P

 

N

P

 

 

N

 

P

 

504

 

15

 

35

 

65

150

150

360

 

 

 

 

 

 

 

 

 

754

 

5

 

15

 

35

75

 

70

175

 

250

 

 

 

 

 

 

 

1104

 

 

 

 

 

 

15

35

 

35

75

 

100

250

 

 

225

 

 

 

1504

 

 

 

 

 

 

10

20

 

20

45

 

60

150

 

 

150

 

275

 

2004

 

 

 

 

 

 

 

 

 

 

 

 

 

35

85

 

 

85

 

200

 

Natural Gas

– 1,000 BTU/ft3, 0.60 specific gravity at 0.5 in. WC pressure drop

 

 

 

 

 

 

 

 

Propane Gas – 2,500 BTU/ft3, 1.53 specific gravity at 0.6 in. WC pressure drop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table I: Maximum Equivalent Pipe Length

 

 

 

 

 

 

When connecting additional gas utilization equipment

• National Electrical Code and any other national,

to the gas piping system, the existing piping must be

 

state, provincial or local codes or regulations hav-

checked to determine if it has adequate capacity for

 

ing jurisdiction.

 

 

 

 

 

 

the combined load.

 

 

 

 

• Safety wiring must be NEC Class 1.

 

The gas valve pressure regulator on the heater is

• Heater must be electrically grounded as required

 

by the NEC.

 

 

 

 

 

 

nominally preset as noted in Table J.

 

 

• In Canada, CSA C22. 1 C.E.C. Part 1.

 

During normal operation, carbon dioxide should be 8.5

The MVB 504-1504 heaters are wired for 120 VAC, 12

to 9.0% at full fire for natural gas and between 9.5 and

amps while the MVB 2004 heaters are wired for 120

10.0% for propane gas. Carbon monoxide should be

VAC, 18 amps. Consult the wiring diagram shipped

‹100ppm.

 

 

 

 

 

 

 

 

 

with the heater. Before starting the heater, check to

 

 

 

 

 

 

 

 

 

 

 

 

ensure proper voltage to the heater and pump.

 

 

Model

 

 

 

Manifold Gas Pressure

 

 

 

 

 

 

 

Boiler mounted pumps (up to

34

 

 

 

 

No.

 

 

 

(High Fire Values)

 

 

⁄ hp) get their power

 

 

 

 

 

 

 

 

 

 

supply directly from the boiler power supply (connec-

 

 

 

Natural Gas

 

Propane Gas

 

 

 

 

 

 

tions in rear wiring box). Install a circuit breaker sized

 

504

 

 

 

-0.1

 

 

 

-0.1

 

sufficiently for both the heater and the pump. Pumps

 

 

 

 

 

 

 

 

 

 

 

 

larger than

34 hp must use a separate power supply

 

754

 

 

 

-0.4

 

 

 

-0.1

 

 

 

 

 

 

 

 

 

and run the power through the optional pump contac-

 

 

 

 

 

 

 

 

 

 

 

 

tor which is located in the rear wiring box. Use

 

1104

 

 

 

-1.0

 

 

 

-0.2

 

 

 

 

 

 

 

 

 

appropriately-sized wire as defined by NEC, CSA

 

1504

 

 

-2.4

 

 

 

-0.6

 

and/or local codes. All primary wiring should be 125%

 

2004

 

 

-1.0

 

 

 

-0.5

 

of minimum rating.

 

 

 

 

 

 

 

NOTE: Manifold pressures should be ±0.2 in. WC.

 

 

If any of the original wire as supplied with the heater

 

 

 

 

Table J: Manifold Gas Pressure Settings

 

must be replaced, it must be replaced with 105°C wire

 

CAUTION:

For proper operation, no more than a

or its equivalent.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30% drop in gas supply pressure from no-load to full-

All high voltage wiring connections to the MVB heater

 

load conditions

 

is acceptabl e.

Under

no

are made inside the rear wiring box as shown in Fig.

 

circumstances should the pressure be outside the

18.

Pump power should be taken from terminals 2

 

listed operational range.

 

 

 

 

(Com), 3 (GND) and 6 (Hot) – 34

hp and smaller ONLY.

 

 

 

 

 

 

 

 

 

 

 

 

Power to the MVB heater should be connected to ter-

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Power Connections

minals 1, 2, and 3 as noted in Fig. 18. All low voltage

wiring, including sensors, interlocks, enable/disable,

Installations must follow these codes:

 

 

and various options are wired into terminals 1–20 on

 

 

the front wiring panel as noted in Fig. 18.

 

20

Page 20
Image 20
Raypak 5042004 Electrical Power Connections, Model, 1 in. NPT, 1-1/4in. NPT, 1-1/2in. NPT, 2 in. NPT, 2-1/2in. NPT