| Water Heater (WH1) |
| |
| Item | Modes | Default Setting | Range | |
| Boil Target |
| 2 | 140°F | OFF, 70 to 190°F |
|
| 3, 7 | 160°F | OFF, 70 to 190°F | |
| Boil Max | 2, | 3, 6, 7 | 180°F | OFF, 120 to 190°F |
| Boil Min | 2, 3, 7 | 135°F | OFF, 80 to 180°F | |
| ‘Burner’ Delay |
| All | 0:00 min | 0:00 to 3:00 min |
| Boil Mass |
| All | 1 (Low) | 1 (Low), 2 (Med), 3 (High) |
| Diff | 2, 3, 7 | Auto | Auto, 2 to 42°F | |
| DHW Target |
| 3 | 120°F | OFF, 70 to 190°F |
| DHW Diff |
| 3 | 5°F | 2 to 10°F |
| ‘Pump’ Dly |
| All | 3:00 min | OFF, 0:20 to 9:55 min, ON |
| Units |
| All | °F | °F or °C |
| Mode |
| N/A | 3 | 2, 3, 7 |
| External Input Signal |
| 7 | 2 to 10 VDC | 2 to 10 VDC or 0 to 10 VDC |
| Offset |
| 7 | 0°F |
Table S: Modulating Temperature Control Default
EXTERNAL INPUT SIGNAL – Selects external input signal range
installing a 500 Ω resistor on the external input signal device’s terminals.
FP - Flame proof warning.
MODE - Operating mode of the heater.
OFFSET - The Offset setting allows the boiler target temperature to be fine tuned to the external input sig- nal. The control reads the external input signal and converts this to a boiler target temperature. The Offset setting is then added to the boiler target temperature. OUTDR - Outdoor air temperature.
OUTDR DESIGN - Design outdoor air temperature used in the heat loss calculation.
OUTDR START - Starting outdoor air temperature. PUMP DLY - Sets the operating time of the pump once the CFH is satisfied.
TANK - Current DHW tank temperature (Mode 3). TANK DIFF - Storage tank differential (Mode 3). TANK TARGET - Target temperature in the DHW storage tank (Mode 3).