| Boiler (H7) |
|
|
| |
|
|
|
|
|
|
| ||
| Item |
| Modes |
| Default Setting | Range |
| |
|
|
|
| |||||
|
|
| 2 |
| 140°F | OFF, | 70 to 220°F |
|
| Boil Target |
| 3 |
| 160°F | OFF, | 70 to 190°F |
|
|
|
| 5, 7 |
| 180°F | OFF, 70 to 220°F |
| |
| Boil Max |
| 2, 5, 7, 8 |
| 200°F | OFF, 120 to 225°F |
| |
|
| 3 |
| 180°F | OFF, 120 to 190°F |
| ||
| Boil Min |
| 2, 3, 5, 7 |
| 135°F | OFF, 80 to 180°F |
| |
| ‘Burner’ Delay |
| All |
| 0:00 min | 0:00 to 3:00 min |
| |
| Boil Mass |
| All |
| 1 (Low) | 1 (Low), 2 (Med), 3 (High) |
| |
| Diff |
| 2, 3, 5, 7 |
| Auto | Auto, 2 to 42°F |
| |
| DHW Target |
| 3 |
| 120°F | OFF, 70 to 190°F |
| |
| DHW Diff |
| 3 |
| 5°F | 2 to 10°F |
| |
| ‘Pump’ Dly |
| All |
| 3:00 min | OFF, 0:20 to 9:55 min, ON |
| |
| Outdr Start |
| 5 |
| 70°F | 35 to 85°F |
| |
| Outdr Design |
| 5 |
|
| |||
| Boil Start |
| 5 |
| 135°F | 35 to 150°F |
| |
| Boil Dsgn |
| 5 |
| 180°F | 120 to 220°F |
| |
| WWSD |
| 5 |
| 70°F | 35 to 100°F |
| |
| Units |
| All |
| °F | °F or °C |
| |
| Mode |
| N/A |
| 2 | 2, 3, 5, 7, 8 |
| |
| External Input Signal |
| 7 |
| 2 to 10 VDC | 2 to 10 VDC or 0 to 10 VDC |
| |
| Offset |
| 7 |
| 0°F |
| ||
| Table |
| Q: Temperature Control Default |
|
| |||
|
|
|
| |||||
|
|
| Pool Heater (P, WHP) |
|
|
| ||
| Item |
| Modes |
| Default Setting | Range |
| |
| Boil Target | 2 |
| 78°F | OFF, 45 to 106°F |
| ||
| Boil Max | 2 |
| 86°F | OFF, 70 to 106°F |
| ||
| Boil Min | 2 |
| 70°F | OFF, 45 to 106°F |
| ||
| ‘Burner’ Delay |
| All |
| 0:00 min | 0:00 to 3:00 min |
| |
| Boil Mass |
| All |
| 1 (Low) | 1 (Low), 2 (Med), 3 (High) |
| |
| Diff | 2 |
| 1°F | 1 to 3°F |
| ||
| ‘Pump’ Dly |
| All |
| 3:00 min | OFF, 0:20 to 9:55 min, ON |
| |
| Units |
| All |
| °F | °F or °C |
| |
| Mode |
| N/A | 2 |
| 2 |
|
Table R: Temperature Control Default