Raypak Y-200 manual Description, Factory Default, Table E Control Screens

Models: Y-200

1 40
Download 40 pages 56.96 Kb
Page 13
Image 13
Control Screens

Control Screens

To access programming mode: Press and hold the "MODE" button for 4 seconds. When in Program mode, cursor is blinking on first settable parameter. UP/DOWN arrows change parameter. LEFT/RIGHT arrows move to next selectable parameter.

NOTE: Once programming is finished, go to Screen 28 to program the USER DEFAULT SET_UP. Then open the front panel and press the SW3 reset button on the motherboard to save the new programming.

SCREEN

DESCRIPTION

FACTORY DEFAULT

Initial Screen

01

Displays the product identification and version of software.

 

Calendar, Time, Initial

 

The present month, day, year and time in a 24-hour clock

 

Setpoint

02

format; setpoint temperature.

 

 

 

 

Temperature can be displayed in degrees Fahrenheit or

 

°F or °C

02

 

Celcius

 

Default value = ° F

 

 

40 to 220 °F (4.4 to 104.4 °C); the system output

 

 

 

temperature desired when the outdoor temperature is 70 °F

 

 

 

(21.1°C); or in domestic hot water applications, the desired

Default = 140 °F

Setpoint

02

 

water temperature.

 

(60°C)

 

 

1 to 10°F; the temperature above and below the Target

 

 

 

Temperature at which the boiler turns off and on. NOTE: The

 

 

 

Control Band is disabled in PID operation. If the Control

 

 

 

Band is adjusted during PID operation, it disables the PID

Default = 3° F. No

Control Band

03

 

function.

 

value when in PID

 

 

Degrees of offset added to or subtracted from the initial set

 

Offset

04

point at the date and time selected.

 

Default = OFF

Setting Holiday

05

Data from screen 04 is combined with these screen settings.

Default = 00-00-RH

 

 

None (for Domestic Hot Water Application ONLY) or 0.01:1 to

 

 

 

8:1; determines how much the internally-calculated Target

Default value =

 

 

Temperature will change for a given outdoor temperature

200°F@10°F

Reset Ratio

06

 

change.

 

(93.3°C@-12.2°C)

System Status

07

Shows the status of the system.

 

 

 

 

 

 

 

Max default value=

 

 

 

 

 

180°F / 82.2°C

 

 

Maximum "USER" water temperatures 235°F (112.7°C) and

Min default value=

Water Temperature

 

Minimum water temperatures 40°F (4.4°C)

Display

105°F / 40.5 °C

Limits

08

 

Only.

 

Changes: Screen 23.

 

 

32 to 200°F (0 to 93.3°C), a warm-weather shutdown feature.

 

Outdoor Cut-off

 

When the outdoor temperature exceeds this setting, the

Default value = 75 °F

Temperature

09

boiler will not fire unless placed in manual override mode.

(23.8°C)

 

 

-01 to -10°F; the number of degrees below the Outdoor Cut-

 

Outdoor Cut-off

 

off Temperature which causes the Outdoor Cut-off

 

Deadband

10

 

Temperature to reset.

 

Default value = -3°F

 

 

Displays the Pump, Boiler, Stage and Auxiliary contact

This screen is

System/Network Monitor

11

status. If flashing, contacts are closed (ON).

DISPLAY only.

 

 

Displays the current Outdoor Air, System Water and Target

 

Outdoor Water TAR

12

Temperature in degrees °F or °C.

 

Default = °F

 

 

000 to 600 seconds; determines when the pump shuts off

 

AUX Delay

13

after entering Outdoor Cut-off mode.

 

Default = 180 seconds.

 

 

0 to 600 seconds; sets the time interval between sequential

 

 

 

boiler start-ups.

0 to 600 seconds;

Default = 10 seconds.

Boiler/Stage On Delay

14

sets time interval between stages turning on.

Disabled in PID.

Table E: Control Screens

13

Page 13
Image 13
Raypak Y-200 manual Description, Factory Default, Table E Control Screens