Control Screens
To access programming mode: Press and hold the "MODE" button for 4 seconds. When in Program mode, cursor is blinking on first settable parameter. UP/DOWN arrows change parameter. LEFT/RIGHT arrows move to next selectable parameter.
NOTE: Once programming is finished, go to Screen 28 to program the USER DEFAULT SET_UP. Then open the front panel and press the SW3 reset button on the motherboard to save the new programming.
SCREEN
DESCRIPTION
FACTORY DEFAULT
Initial Screen | 01 | Displays the product identification and version of software. |
| ||
Calendar, Time, Initial |
| The present month, day, year and time in a |
| ||
Setpoint | 02 | format; setpoint temperature. |
|
| |
|
| Temperature can be displayed in degrees Fahrenheit or |
| ||
°F or °C | 02 |
| Celcius |
| Default value = ° F |
|
| 40 to 220 °F (4.4 to 104.4 °C); the system output |
| ||
|
| temperature desired when the outdoor temperature is 70 °F |
| ||
|
| (21.1°C); or in domestic hot water applications, the desired | Default = 140 °F | ||
Setpoint | 02 |
| water temperature. |
| (60°C) |
|
| 1 to 10°F; the temperature above and below the Target |
| ||
|
| Temperature at which the boiler turns off and on. NOTE: The |
| ||
|
| Control Band is disabled in PID operation. If the Control |
| ||
|
| Band is adjusted during PID operation, it disables the PID | Default = 3° F. No | ||
Control Band | 03 |
| function. |
| value when in PID |
|
| Degrees of offset added to or subtracted from the initial set |
| ||
Offset | 04 | point at the date and time selected. |
| Default = OFF | |
Setting Holiday | 05 | Data from screen 04 is combined with these screen settings. | Default = | ||
|
| None (for Domestic Hot Water Application ONLY) or 0.01:1 to |
| ||
|
| 8:1; determines how much the | Default value = | ||
|
| Temperature will change for a given outdoor temperature | 200°F@10°F | ||
Reset Ratio | 06 |
| change. |
| |
System Status | 07 | Shows the status of the system. |
|
| |
|
|
|
|
| Max default value= |
|
|
|
|
| 180°F / 82.2°C |
|
| Maximum "USER" water temperatures 235°F (112.7°C) and | Min default value= | ||
Water Temperature |
| Minimum water temperatures 40°F (4.4°C) | Display | 105°F / 40.5 °C | |
Limits | 08 |
| Only. |
| Changes: Screen 23. |
|
| 32 to 200°F (0 to 93.3°C), a |
| ||
Outdoor |
| When the outdoor temperature exceeds this setting, the | Default value = 75 °F | ||
Temperature | 09 | boiler will not fire unless placed in manual override mode. | (23.8°C) | ||
|
|
| |||
Outdoor |
| off Temperature which causes the Outdoor |
| ||
Deadband | 10 |
| Temperature to reset. |
| Default value = |
|
| Displays the Pump, Boiler, Stage and Auxiliary contact | This screen is | ||
System/Network Monitor | 11 | status. If flashing, contacts are closed (ON). | DISPLAY only. | ||
|
| Displays the current Outdoor Air, System Water and Target |
| ||
Outdoor Water TAR | 12 | Temperature in degrees °F or °C. |
| Default = °F | |
|
| 000 to 600 seconds; determines when the pump shuts off |
| ||
AUX Delay | 13 | after entering Outdoor |
| Default = 180 seconds. | |
|
| 0 to 600 seconds; sets the time interval between sequential |
| ||
|
| boiler | 0 to 600 seconds; | Default = 10 seconds. | |
Boiler/Stage On Delay | 14 | sets time interval between stages turning on. | Disabled in PID. |
Table E: Control Screens