Outdoor reset function should be disabled. See screen 06 and 24.

Power Test

Check Power

Utilizing a Volt-ohm meter (VOM) monitor the following on the controller for proper voltage levels. Check at the Terminal Block (TB-1).

From

To

Indication

TB pin 1

TB pin 2

108 VAC to 132

VAC

TB pin 1

Single Point

108 VAC to 132

Ground

VAC

TB pin 2

Single Point

Less than 0.6 VAC

Ground

Table C: Voltage Measurements