Auxiliary Delay:
|
|
|
| Screen number |
A U X | D E L | A | Y | 1 3 |
| X | X | X | S E C |
Auxiliary Delay
When CFH signal is "ON" the relay contact of the A1 Auxiliary module stays closed. When the CFH signal changes to "OFF", the contacts of the relay stay closed as long as the delay is set up.
The AUX contacts operate on a delay after CFH.
AUX turnoff range is 0 to 600 seconds. The default value is 180 seconds.
NOTE: If the
INSTALLERS NOTE: If the end user requires the "System Pump" to be turned off if the "CFH" or "Safety" signal is removed, it is recommended that the system pump be operated from the "Aux 1 Relay", to provide a delay on turn off.
Boiler/Stage ON Delay:
NOTE: Refer to screen number 16 (standard)
B O I L R / S T G
X X X S E C
Boiler Turn-On Delay
In a multiple boiler system: The boiler
The Boiler
Factory default is 30 seconds.
|
|
|
|
| Screen number |
O N | D | L | Y |
| 1 4 |
X | X X |
| S | E | C |
Stage Turn-On Delay
The Stage
The Stage
Recommended Initial setting stage for
Factory default is 10 seconds.
25