Holiday:
|
|
|
|
| Screen number |
S E T T I N G | H O L | I | D A Y | 0 5 | |
H O L # X X | X X — X X — X X |
| |||
Thirty two holidays are | Month: | Day: |
| Year: |
|
selectable | 01 thru 12 | 01 thru 31 | 01 to 99; Below 01 is | ||
|
|
|
| Repeating Holiday (RH) setting |
NOTE: Previous screen (04) is used for entering the offset value in degrees.
Reset Ratio:
Ratio of outdoor temperature to water system
temperature. Range: . 01:1 to 8:1 or "None" forScreen number constant water temperature
(then TARGET=SETPOINT). Default value is 1.00:1.
R | S | T | R | A T | I O | X . X | X : | 1 | 0 6 |
X | X | X | . X | @ 7 | 0 | X X | X . | X @ X X |
Default:
System temperature at 70°F (21.1°C) 140°F @ 70°F (60°C @ 21.1°C)
NOTE: The reset ratio can be modified by changing either the ratio value in line #1 or the system temperature value in line #2.
NOTE: When the reset ratio selected is "NONE", line 2 disappears.
NOTE: Use reset ratio "NONE" when using this controller for domestic hot water or pool applications.
The Reset Parameter
Sets the desired change in system. Water temperature increases as the outdoor temperature decreases. The reset ratio selector is used to determine the rate of change of the boiler(s) output water temperature rela- tive to a change in the outdoor temperature. The first number of the ratio refers to the outdoor temperature
Default:
System temperature at °F
This value is 200°F @ 10°F (93.3°C @
and the second number refers to the degree(s) of change for the water temperature, e.g., a ratio of 2:1 means for every 2° change in outdoor temperature, the System Temperature will change 1°. (The reset temp cannot exceed the temp limits set on screen #08.)
Example: Setpoint = 135°F
Ratio | Temperature °F | |
Outdoor | System | |
| 70 | 135 |
2:1 | 60 | 140 |
40 | 150 | |
| 20 | 160 |
Table G: Outdoor to System Temperature Ratio
20