Fig. 10: System to Outdoor Temperature
| Typical | Reset Ratio Setpoint at Design Temp: | |||||
Radiation | Temp@ | Temp@ |
|
|
|
|
|
Design Cond. | 70°F | 40°F |
| 20°F | 0°F | ||
|
|
|
|
|
|
|
|
Standing | 190 | 105 | 0.3:1 |
| 0.6:1 | 0.8:1 | 1.1:1 |
Convection or |
|
|
|
|
|
|
|
Baseboard | 200 | 105 | 0.3:1 |
| 0.5:1 | 0.7:1 | 0.9:1 |
Fan coil |
|
|
|
|
|
|
|
Heating | 190 | 105 | 0.3:1 |
| 0.6:1 | 0.8:1 | 1.1:1 |
Fan Coil |
|
|
|
|
|
|
|
Heat and Cool | 140 | 105 | 0.9:1 |
| 1.4:1 | 2.0:1 | 2.6:1 |
|
|
|
|
|
|
|
|
Radiant |
|
|
|
|
|
|
|
Floor | 120 | 105 | 2.0:1 |
| 3.3:1 | 4.7:1 | 6.0:1 |
Radiant |
|
|
|
|
|
|
|
Ceiling | 120 | 105 | 2.0:1 |
| 3.3:1 | 4.7:1 | 6.0:1 |
| Table H: Suggested Guidelines |
|
|
|
21