Boiler/Stage Off Delay:

Boiler/Stage Off Delay:

B O I L R / S T G

X X X S E C

Boiler Turn-Off Delay

In a multiple boiler system: The boiler Turn-Off Delay sets the amount of delay before each additional boiler is turned off. This delay starts when the preceding boil- er is turned off.

The Boiler Turn-Off Delay range is from 0 to 600 sec- onds.

Recommended Initial setting for Boiler Turn-Off Delay is 30 seconds.

Factory default is 30 seconds.

 

 

 

 

 

Screen number

O F

F

 

D L

Y

1 5

X

X

X

S

E

C

Stage Turn-Off Delay

The Stage Turn-Off Delay sets the time delay before a stage in a multi-stage boiler configuration is turned off. This delay starts when the stage or boiler preceding the next stage is turned off.

The Stage Turn-Off Delay range is from 0 to 600 sec- onds.

Recommended Initial setting stage for Turn-Off Delay is 10 seconds.

Factory default is 10 seconds.

Proportional Integral Derivative (PID)

 

 

 

 

 

 

 

 

Screen number

P

I

D

C =

X X

X

S

= X X

1 6

P

=

X

X X

D

=

X X X

I

= X X X

NOTE: PID mode is logic control for microprocessor; disables screens 3, 14 and 15.

Standard:

This is the factory default screen.

Screen number

S T A N D A R D

1 6

Standard mode is controlled by:

Screen 3: Control Band

Screen 14: Time On Delay

Screen 15: Time Off Delay