Boiler/Stage Off Delay:
B O I L R / S T G
X X X S E C
Boiler Turn-Off Delay
In a multiple boiler system: The boiler
The Boiler
Recommended Initial setting for Boiler
Factory default is 30 seconds.
|
|
|
|
| Screen number |
O F | F |
| D L | Y | 1 5 |
X | X | X | S | E | C |
Stage Turn-Off Delay
The Stage
The Stage
Recommended Initial setting stage for
Factory default is 10 seconds.
Proportional Integral Derivative (PID)
|
|
|
|
|
|
|
| Screen number |
P | I | D | C = | X X | X | S | = X X | 1 6 |
P | = | X | X X | D | = | X X X | I | = X X X |
NOTE: PID mode is logic control for microprocessor; disables screens 3, 14 and 15.
Standard:
This is the factory default screen.
Screen number
S T A N D A R D | 1 6 |
Standard mode is controlled by:
Screen 3: Control Band
Screen 14: Time On Delay
Screen 15: Time Off Delay
26