INSTALLATION
FACING & FINISHING REQUIREMENTS
This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a non- combustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
Top Standoff Assembly
The top standoffs are shipped in a flat position and must be folded into shape and attached.
1) Remove the standoffs from the fireplace top.
2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the
3) Attach the standoff securely to the top with
4 screws per standoff (on opposite cor- ners).
VENTING
INTRODUCTION
The
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent sys- tems are prohibited.
Regency | 11 |