INSTALLATION
VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON
The diagram below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow).
Note:
1) A maximum of three 90o elbows are permitted.
2) Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed on page 9.
•Horizontal vent must be supported every 3 feet.
•Firestops are required at each floor level and whenever passing through a wall.
•Must use optional flue adapter (Part#
•A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Straight Out Horizontal Venting | Horizontal Venting with One (1) 90o Elbow | ||
| Option | V | H |
| A) | 1' (305mm) Minimum | 3' (914mm) Maximum |
| B) | 2' (610mm) Minimum | 6' (1.86m) Maximum |
| C) | 3' (914mm) Minimum | 9' (2.7m) Maximum |
| D) | 4' (1.22m) Minimum | 12' (3.6m) Maximum |
| E) | 5' (1.5m) Minimum | 15' (4.5m) Maximum |
| F) | 6' (1.86m) Minimum | 17' (5.1m) Maximum |
| With the above options, maximum total pipe length if 37 feet with | ||
| minimum of 6 feet total vertical and maximum 17 feet total horizontal. | ||
| Please note minimum 1 foot between 90o elbows is required. |
Diagram 1
Diagram 2
Please note the minimum centerline for basic install shown above.