![HORIZONTAL](/images/new-backgrounds/51057/5105737x1.webp)
INSTALLATION
Vertical Venting with Three (3) 90o Elbows
| Option |
| V + V1 | H + H1 | |
| A) | 2' (610mm) Minimum | 3' (914mm) Maximum | ||
| B) | 3' (914mm) Minimum | 6' (1.86m) Maximum |
| |
| C) | 4' | (1.22m) Minimum | 9' (2.7m) Maximum | |
| D) | 5' | (1.5m) Minimum | 12' (3.6m) Maximum | |
|
|
|
|
|
|
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 12
HORIZONTAL
INSTALLATIONS
Install the vent system according to the manufacturer's instructions included with the components.
gram 1. Push the pipe sections com- pletely together, then
1)Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is at- tached. If this is the case, you may want to adjust the location of the unit. Rough in the gas.
2)Direct Vent pipe and fittings are designed with special
3)Put a bead of silicone inside the outer section of the adapter and a bead of Mill Pac on the inner collar. Slip the adapter over the exist- ing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
4)Assemble the desired combination of pipe and elbows to the appliance adaptor and
Note:
a)
Diagram 1
Note: Apply sealant
b)Horizontal runs of vent must be sup- ported every three feet. Wall straps are available for this purpose.
5)Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be termi- nated. If the wall being penetrated is con- structed of
Note: With
Diagram 2
Note:
a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.
b)The location of the horizontal vent ter- mination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see diagram on page 12.
6)The arrow on the vent cap should be pointing up. Insure that the
The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Note: If installing termination on a siding covered wall, a vinyl siding stand- off or furring strips must be used
Regency | 19 |