INSTALLATION
This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/ blower operation.
WIRING
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.
CAUTION: Label all wires prior to disconnection when servicing con- trols. Wiring errors can cause im- proper and dangerous operation.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded
OPTIONAL WALL
THERMOSTAT
A wall thermostat may be installed if desired. Connect the wires as per the wiring diagrams. Note that the wires are connected to the "TH" on the gas valve. Use table below to determine the maximum wire length:
Note: Preferable if the thermostat is in- stalled on an interior wall.
Regency offers an optional programmable ther- mostat but any
CAUTION
Do not connect the millivolt
wall thermostat wires to the 120V wires.
Thermostat Wire Table
Recommended Maximum Lead Length
Thermostat
| Wire Size | Max. Length | ||
|
|
|
|
|
| 14 GA. | 50 | Ft. | |
| 16 GA. | 32 | Ft. |
|
| 18 GA. | 20 | Ft. | |
| 20 GA. | 12 | Ft. | |
| 22 GA. | 9 | Ft. | |
|
|
|
|
|
OPTIONAL REMOTE
CONTROL
Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty.
The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.
1)Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very im- portant). Run wires from the fireplace to that location, use Thermostat Wire Table.
2)Connect the wires as per the wiring dia- gram above.