Rinnai RHFE-308 FTR Location, Flue Sizes, Snow Areas, Standard Installation Of Flue Manifold

Models: RHFE-308 FTR

1 48
Download 48 pages 44.64 Kb
Page 25
Image 25
FLUE SIZES:

LOCATION

Do not flue into natural draught flues or fireplaces, this unit can only be used with one of the six types of Rinnai flue kits.

Do not flue unit into other rooms. Flue terminal must be outside.

Flue may be positioned directly under opening windows, with a minimum clearance of 300mm.

FLUE SIZES:

6 Flue lengths are available.

 

 

S

flue suits wall

75

-

115 mm

A

flue suits wall

115

-

240 mm

B

flue suits wall

240

-

400 mm

C

flue suits wall

400

-

600 mm

D

flue suits wall

600

-

800 mm

E

flue suits wall

800

-

1000 mm

Co-ax flue also available.

SNOW AREAS

Snow

In areas subject to heavy snowfall, keep snow clear of flue terminal at all times.

STANDARD INSTALLATION OF FLUE MANIFOLD.

Diagram below shows minimum clearances and distances from obstructions. Also check local regulations.

Flammable

 

Non

 

Flammable

600mm

Wall

 

300mm

 

375mm

600mm

Opposite

 

Wall

 

Floor

Side Clearances

300mm

Obstruction

FIT BACK COVERS (SIDES ONLY)

Fit back covers (sides only) as shown below.

Secure with

Screws

Secure with Screws

GAS CONNECTION

Fit suitable copper flare elbow to appliance inlet.

– 25 –

Page 25
Image 25
Rinnai RHFE-308 FTR Location, Flue Sizes, Snow Areas, Standard Installation Of Flue Manifold, Fit Back Covers Sides Only