SECTION 11: OPERATION AND MAINTENANCE
SECTION 11: OPERATION AND MAINTENANCE
DANGER |
| WARNING |
| |
Electrical Shock Hazard | Explosion Hazard | Burn Hazard | Cut/Pinch Hazard | |
Disconnect electric | Turn off gas supply to | Allow heater to cool | Wear protective gear | |
heater before service. | before service. | during installation, | ||
before service. | ||||
|
| operation and service. | ||
Heater must be |
| Tubing may still be hot | ||
|
| |||
connected to a properly |
| after operation. | Edges are sharp. | |
grounded electrical |
|
|
| |
source. |
|
|
|
Failure to follow these instructions can result in death, electric shock, injury or property damage.
This heater is equipped with a direct spark ignition | 8. When thermostat is satisfied, all power to the |
system. | unit is shut off. |
11.1 Sequence of Operation
1.Turn the thermostat up. When the thermostat calls for heat, the blower motor will energize.
2.When the motor approaches nominal running RPM, the pressure switch closes and activates the ignition module.
3.After a 45 second prepurge, the ignition module then opens the gas valve and energizes the spark igniter.
4.When the flame is established, the sparking sequence ceases.
5.If the flame is not established during the ignition sequence, the ignition module closes the gas valve and purge begins. Module will try 2 additional times for ignition (with purges in between trials). If ignition is not established, the module will lockout.
6.If the flame extinguishes during operation, the ignition module will attempt the multiple trial sequence described in step 5. If ignition is not
7.After lockout, the control can be reset by turning down thermostat for five seconds, and then raising it again to desired temperature, or by disconnecting power and then reconnecting.
11.2 To Shut Off Heater
Set thermostat to lowest setting. Turn OFF electric power to heater.
Turn OFF manual gas valve in the heater supply line.
11.3 To Start Heater
Turn gas valve and electric power OFF and wait five minutes for unburned gases to vent from heater. Turn ON main gas valve.
Turn ON electric power.
Set thermostat to desired temperature. Burner should light automatically.
11.4Pre-Season Maintenance and Annual Inspection
To ensure your safety and years of
Turn off gas and electric supplies before performing service or maintenance. Allow heater to cool before servicing.
Before every heating season, a contractor qualified in the installation and service of
For best performance, the gas, electrical, thermostat connections, tubing, venting, suspensions and