BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

overall heater condition should be thoroughly inspected.

NOTE: Gas flow and burner ignition are among the first things that should be throughly inspected. Please see Page 48, Section 11.5 for suggested items to inspect.

11.5 Maintenance Checklist

Installation Code and Annual Inspections:

All installation and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon LLC and

conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service, operation and labeling of the equipment.

To help facilitate optimum performance and safety, Roberts-Gordon LLC recommends that a qualified contractor conduct, at a minimum, annual inspections of your ROBERTS GORDON® equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts- Gordon LLC.

The Vicinity of the Heater

Do not store or use flammable objects, liquids or vapors near the heater.

 

Immediately remove these items if they are present.

 

See Page 5, Section 3.

 

 

Vehicles and Other

Maintain the clearances to combustibles.

Objects

Do not hang anything from, or place anything on, the heater.

 

 

Make sure nothing is lodged underneath the reflector, in between the tubes or

 

in the decorative or protective grilles (included with select models).

 

Immediately remove objects in violation of the clearances to combustibles.

 

See Page 5, Section 3.

 

 

Reflector

Support reflector with reflector hanger and support strap.

 

Reflector must not touch tube.

 

Make sure there is no dirt, sagging, cracking or distortion.

 

Do not operate if there is sagging, cracking or distortion.

 

Make sure reflectors are correctly overlapped. See Page 23, Section 6.5.1.

 

Clean outside surface with a damp cloth.

 

 

Vent Pipe

Venting must be intact. Using a flashlight, look for obstructions, cracks on the

 

pipe, gaps in the sealed areas or corrosion.

 

The area must be free of dirt and dust.

 

Remove any carbon deposits or scale using a wire brush.

 

See Page 35, Section 8.

 

 

Outside Air Inlet

Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the

 

sealed areas or corrosion.

 

The area must be free of dirt and dust. Clean and reinstall as required.

 

 

Tubes

Make sure there are no cracks.

 

Make sure tubes are connected and suspended securely.

 

See Page 14, Section 6.

 

Make sure there is no sagging, bending or distortion.

 

Clean or replace as required.

 

 

Gas Line

Check for gas leaks. See Page 41, Section 9.

 

 

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

48 of 59

Page 54
Image 54
Roberts Gorden BH-115 Vicinity of the Heater, Vehicles and Other, Objects, Reflector, Vent Pipe, Outside Air Inlet, Tubes