BH-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

8.2 Unvented Operation

Sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3 cfm per 1000 Btu/h firing rate (Canada).

Use of optional outside combustion air is not recommended with unvented heaters.

If exhaust fans are used to supply ventilation air, an interlock switch must be used to prevent the heater from coming on when the fans are off. This may be done using a pressure switch.

8.3 Horizontal Venting

In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.

For 4" (10 cm) vents in either combustible or noncombustible walls, use Tjernlund VH1-4 (P/N 90502100) or equivalent, insulated vent terminal. Follow the manufacturer's instructions for proper installation.

For 6" (15 cm) common vents in either combustible or noncombustible walls, use Tjernlund VH1-6 (P/N 90502101) or equivalent, insulated vent terminal.

Follow the manufacturer's instructions for proper installation.

8.4 Vertical Venting

For 4'' (10 cm) common vent, an approved vent cap (P/N 90502300) must be used.

For 6'' (15 cm) common vent, an approved vent cap (P/N 90502302) must be used.

For common vertical venting of more than two heaters, See Page 38, Section 8.10.

A vent shall not extend less than 2' (0.6m) above the highest point where it passes through a flat roof of a building.

8.5 Unvented Operation Tube Termination

Turndown type vent terminal with a screen must be installed at the exhaust end of the tube. Vent terminal design shall not incorporate backdraft flap.

FIGURE 22: Tube Termination

8.6 Length Requirements

The maximum vent length allowed is 45' (13.7 m). The maximum outside air supply duct length allowed is 45' (13.7 m).

The total vent length, plus outside air duct length, plus any extensions to minimum heat exchanger lengths, cannot exceed 65' (19.8 m).

Vent length should be limited to less than 20' (6 m). If using vent lengths greater than 20' (6 m), condensation will form in the vent pipe. Insulation and additional sealing measures (high temperature silicone at all seams) are required. Optional heat exchanger beyond minimum lengths is considered as vent length for length determination.

Subtract 15' (4.6 m) of maximum allowed vent or duct length per vent elbow if more than two are used.

8.7 Horizontal Ventilation 4'' (10 cm) Pipe

 

 

SIDE VIEW

 

 

Combustible or

 

Non-Combustible Wall Only

 

Non-Combustible Wall

 

Vent Adapter

 

Vent Adapter

 

 

18" (46 cm)

 

 

 

 

 

 

Min.

4" (10 cm)

 

 

 

Single Wall Pipe

 

 

Vent Terminal

 

 

4" (10 cm) Single Wall Pipe

 

Vent Terminal

 

 

 

 

Description

Part Number

 

 

Vent Terminal (Comb. Wall)

90502100

 

 

Vent Terminal

02537801-XX

 

 

36 of 59

 

 

 

Page 42
Image 42
Roberts Gorden BH-150, BH-60, BH-40, BH-175 Horizontal Venting, Vertical Venting, Unvented Operation Tube Termination