SECTION 4: Specifications

-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

4.6 Linear Heater

 

 

 

 

 

 

 

 

 

BH15ST

BH20ST

BH25ST

BH30ST

BH35ST

BH40ST

BH45ST

BH50ST

 

 

 

 

 

 

 

 

 

Input – kW

15

20

25

30

35

40

45

50

Input – MJ

54

72

90

110

125

138

162

180

Tube Length – mm

6096

9144

9144

12192

12192

12192

15240

15240

Overall Heater Length - mm

6661

9709

9709

12757

12757

12757

15815

15815

Weight – kg

41

55

55

68

68

68

81

81

Heated Area – m2

20-160

30-210

40-265

50-315

55-370

65-420

70-475

80-525

Minimum Installation

2.5

2.5

3.0

3.5

4.6

5.0

5.0

5.0

Height* – m

 

 

 

 

 

 

 

 

Recommended Installation

3.0

3.5

3.9

4.2

4.8

5.5

6.7

7.6

Height* – m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.8 U-Tube Heater

 

 

 

 

 

 

 

 

 

BH15UT

BH20UT

BH25UT

BH30UT

BH35UT

BH40UT

BH45UT

BH50UT

 

 

 

 

 

 

 

 

 

Input – kW

15

20

25

30

35

40

45

50

Input – MJ

54

72

90

110

125

138

162

180

Tube Length – mm

3323

4843

4843

6363

6363

6363

7998

7998

Overall Heater Length - mm

3893

5417

5417

6941

6941

6941

8465

8465

Weight – kg

39

54

54

65

65

66

96

96

Heated Area – m2

20-160

30-210

40-265

50-315

55-370

65-420

70-475

80-525

Minimum Installation

2.5

2.8

3.5

4.0

5.0

5.0

5.0

5.0

Height* – m

 

 

 

 

 

 

 

 

Recommended Installation

3.0

3.5

3.9

4.2

4.8

5.5

6.7

7.6

Height* – m

 

 

 

 

 

 

 

 

*Heights quoted are from ground level to bottom face of firing tube.

NOTE:- Factory recommended mounting heights are listed above as a guideline. If infra-red heaters are mounted too low, they may result in heat discomfort. It is generally recommended to observe the recommended mounting heights to optimize comfort conditions. However, certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings may result in the heaters being mounted outside of the factory recommended mounting heights. Clearances to combustibles must always be maintained.