RuggedCom RX1510 manual EMI And Environmental Type Tests, a RuggedCom-specified severity levels

Models: RX1510

1 45
Download 45 pages 21.18 Kb
Page 42
Image 42
5. EMI And Environmental Type Tests

5. EMI And Environmental Type Tests

5. EMI And Environmental Type Tests

Test

Description

Test Levels

Severity

Levels

 

 

 

 

IEC 61000-4-2

ESD

Enclosure Contact

+/- 8 kV

4

 

 

 

Enclosure Air

+/- 15 kV

4

 

 

 

 

 

 

 

IEC 61000-4-3

Radiated RFI

Enclosure Ports

20 V/m

Notea

 

 

Signal ports

+/- 4kV @ 2.5kHz

Notea

IEC 61000-4-4

Burst (Fast Transient)

D.C. Power ports

+/- 4kV

4

 

 

 

A.C. Power ports

+/- 4kV

4

 

 

 

 

 

 

 

 

 

Earth ground ports

+/- 4kV

4

 

 

 

 

 

 

 

Signal ports

+/- 4kV line-to-earth,

4

 

 

+/- 2kV line-to-line

 

 

 

 

 

 

 

 

 

IEC 61000-4-5

Surge

D.C. Power ports

+/- 2kV line-to-earth,

3

+/- 1kV line-to-line

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

+/- 4kV line-to-earth,

4

 

 

+/- 2kV line-to-line

 

 

 

 

 

 

 

 

 

 

 

Signal ports

10V

3

 

 

 

 

 

IEC 61000-4-6

Induced (Conducted) RFI

D.C Power ports

10V

3

 

 

 

A.C. Power ports

10V

3

 

 

 

 

 

 

 

 

 

Earth ground ports

10V

3

 

 

 

 

 

 

 

 

40 A/m, continuous,

Notea

IEC 61000-4-8

Magnetic Field

Enclosure Ports

1000 A/m for 1 s

 

 

 

 

1000 A/m for 1 s

5

 

 

 

 

 

 

 

D.C. Power ports

30% for 0.1s, 60% for

N/A

 

 

0.1s, 100% for 0.05s

IEC 61000-4-29

Voltage Dips & Interrupts

 

 

 

 

 

A.C. Power ports

30% for 1 period,

N/A

 

 

 

 

60% for 50 periods

 

 

 

 

 

 

 

 

 

IEC 61000-4-11

Voltage Dips & Interrupts

A.C. Power ports

100% for 5 periods,

N/A

100% for 50 periods

 

 

 

 

 

 

 

 

 

 

 

Signal ports

2.5kV common, 1kV

3

 

 

diff. mode@1MHz

 

 

 

 

 

 

 

 

 

IEC 61000-4-12

Damped Oscillatory

D.C. Power ports

2.5kV common, 1kV

3

diff. mode@1MHz

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

2.5kV common, 1kV

3

 

 

diff. mode@1MHz

 

 

 

 

 

 

 

 

 

IEC 61000-4-16

Mains Frequency Voltage

Signal ports

30V Continuous, 300V for 1s

4

 

 

 

D.C. Power ports

30V Continuous, 300V for 1s

4

 

 

 

 

 

 

 

IEC 61000-4-17

Ripple on D.C.

D.C. Power ports

10%

3

Power Supply

 

 

 

 

 

 

 

 

 

 

 

Signal ports

2kVAC (Fail-Safe Relay output)

N/A

 

 

 

 

 

IEC 60255-5

Dielectric Strength

D.C. Power ports

1.5kVDC

N/A

 

 

 

 

 

 

 

A.C. Power ports

2kVAC

N/A

 

 

 

 

 

 

 

Signal ports

5kV (Fail-Safe Relay output)

N/A

 

 

 

 

 

IEC 60255-5

H.V. Impulse

D.C. Power ports

5kV

N/A

 

 

 

 

 

 

 

A.C. Power ports

5kV

N/A

aRuggedCom-specified severity levels

Table 5.1. IEC 61850-3 EMI Type Tests

RuggedCom® RuggedBackbone™

42

RX1510 Installation Guide Rev 104

Page 42
Image 42
RuggedCom RX1510 EMI And Environmental Type Tests, a RuggedCom-specified severity levels, 1. IEC 61850-3 EMI Type Tests