3-3-8 When the 4 way valve (A,B) is not operating

3-3-8 When the 4 way valve (A,B) is not operating

1)Inspection items

(1)Are the 4 way valve A and B under the operating conditions?

(When the COMP A (4 way valve A ) and COMP B (4 way valve B) are on during the heating operating)

(2)Is the power voltage normal?

(3)Is the connecting of 4 way valve A (CN 75) and B (CN 76) good?

2) Inspection sequence

Put off the outdoor unit power and put it on again after 5 seconds.

Select the heating operation of A(B) room by the remote controller.

Has 3 minutes passed after selection of A(B) room heating?

YES

Is the 4 way valve A(B) on?

NO

Is the voltage shown across the 4 way valve A(B) connector

(CN 75, CN 76) ?

NO

Is the pin no 47(46) of IC 04 ( MICOM) at high (DC 5V) ?

NO

Is the 4 way valve A (B) under operating conditions?

NO

Normal

NO

YES

YES

YES

YES

Keep 4 way valve off.

Normal

Defect of RY 76 (RY 77) contact and coil

Replace the Relay

Defect of IC 06 (IC 07 ) output → Replace

Defect of IC 04(MICOM) - replace the IC 04

or PCB ass’y

*4 way valve operating conditions

(1)During the defrost control, put the 4 way valve A(B) off.

(2)During the heating operation put the 4 way valve A(B) on.

(3)The changeover of heating to cooling : put the 4 way valve off immediately (in case of B and C room).

(4)The changeover of cooling to heating : it is on after 170 seconds delay.