3-3-9 When the compressor does not operate

3-3-9 When the compressor does not operate

1)Inspection items

(1)Is the COMP A under the operating conditions? (cooling operating of A, B(C) room)

(2)Is the power voltage normal? (the rating voltage ±10% range)

(3)Are the connector connection of COMP A(RY 72, 73) and B(RY 71) good?

(4)The COMP A(B) is operated on and off in accordance with the operating conditions of indoor unit of A (B. C) room.

2) Inspection sequence

Apply the outdoor power and operate the indoor unit A(B, C)

in the cooling mode.

 

 

 

NO

Is the comp A under the operating condition?

 

 

 

YES

 

 

 

Has 3 minutes passed COMP A(B) after the power initial

NO

and COMP on/off

 

 

YES

 

 

 

Is comp A (B) on?

 

 

 

YES

 

 

 

 

 

 

 

NO *Refer to the power measuring terminal

 

 

 

 

Normal (comp A (B) off)

Keep Comp A (B) off

Normal

Is the voltage (the rating voltage ±10% range) shown across the terminal of Comp A(B) power applied?

YES

Defect of comp A (B) and running condenser

Replace

 

NO

 

Is the voltage of pin no. 14, 13( 15) at low

YES

 

(DC 0.7V)?

 

 

NO

 

 

 

Is the voltage of pin no. 50, 51 (52) of IC 04 (micom) at

YES

 

high (DC 5V)?

 

 

NO

 

 

 

Is comp A (B ) under the operating condition?

YES

 

 

 

NO

 

 

 

 

 

 

Defect of Ry 72, 73 (Comp B) and Ry 71(comp A)

contact and coil → Replace

Defect of IC 06 output

Replace

Defect of Ic 04 (micom)

Replace

Normal (comp A (B ) off)

*Comp A (B ) operating conditions

(1)Comp A : Comp on /off control in accordance with the A room during the heating and cooling indoor unit operation

(2)Comp B : Comp on /off control in accordance with the B(C) room during the heating and cooling

indoor unit operation

BLK

 

(3) RY72 (4)

BLK

* Comp A(B ) power measuring terminal

WHT

 

(1)

Comp A measuring ; RY 73 (4) ´ RY 72 (4)

(3) RY71 (4)

(3) RY73

WHT

(2)

Comp B measuring ; RY 71 (4) ´ RY 72 (4)

(4)

 

 

RED

 

(3)

Power input ; RY 72 (3) ´ RY 73(3)

 