Device List Before you begin, keep in mind the following:
For master mode usage of the COM port:
Modbus devices do not have to be defined in the Device List, but it helps
you manage your system.
Master Mode Device List Setup
If you selected Master mode on the Serial Port page, follow the steps below
to set up the device list:
Figure4: Master Mode Topology
Action Result
1. From the Setup page, click Device List. Opens the Device List page.
2. Select the number of viewable devices (1 to
128), then click Apply.
Selects the number of viewable locations that
can be used to define serial slave devices
connected to the ETG.
3. In the Local ID text box, type the local ID
(address) of the serial slave device. Enters the local address of the device.
4. Repeat step 3 until all of the devices are
entered.
Enters all of the connected devices.
5. Click Apply. Updates the Device List settings.
Figure 5: Device List Page in Master Mode
Ethernet
Connection
RS485 connection
Serial Slave Devices
Up to 128 serial
slave devices
using repeaters
ETG in
master
mode