ConneXiumEthernet Gateway

Setup

Modbus TCP/IP Filtering

63230-319-211A1 2/2006

This function allows the administrator to specify Modbus TCP/IP client devices that have or do not have access to serial slave devices connected to the ETG.

NOTE: There is an anonymous Modbus TCP/IP address (***.***.***.***) that can be set to Read-only or None. Setting it to Read-onlyallows any Modbus TCP/IP client not in the filtered list to access serial slave devices with read-only access. Setting it to None blocks all Modbus TCP/IP clients not in the filtered list.

 

Action

Result

 

 

 

1.

From the Setup page, click Modbus

Opens the Modbus TCP/IP Filtering page.

 

TCP/IP Filtering.

 

 

 

 

2.

Check Enable Filtering.

Activates filtering.

 

 

 

3.

In the IP address column, enter the

Enters an IP address for a Modbus TCP/IP

 

Modbus TCP/IP client address

client that will have access to the serial devices

 

 

connected to the ETG.

 

 

 

4.

In the Access Level column, select Read-

Selects the access level for the corresponding

 

only or Full.

IP address. When set to Read-only, only the

 

 

following Modbus TCP/IP function codes are

 

 

allowed:

 

 

Decimal: 1, 2, 3, 4, 7, 8, 11, 12, 17, 20, 24,

 

 

43, 100

 

 

Hexadecimal: 01, 02, 03, 04, 07, 08, 0B, 0C,

 

 

11, 14, 18, 2B, 64

 

 

 

5.

Repeat steps 3 and 4 to add more IP

Continues adding IP addresses for filtering.

 

addresses.

 

 

 

 

6.

Click Apply.

Saves the Modbus TCP/IP address filtering list.

 

 

 

Figure 10: Modbus TCP/IP Filtering Page