The controller is located at the front of the unit,

Control Safeties:

under the top panel.

 

It is powered by a 12 volt transformer. It has 5 indicator lights:

Compressor - Light is ON if compressor is powered

Water - Light is ON if inlet water solenoid valve is powered

Hot Gas - Light is ON when Hot Gas Valve is powered

Fan - Light is ON when Fan motor is powered

Power - Light is ON when power is connected to controller

No Water. If the Water Sensor cannot detect water, and the inlet water solenoid valve has been on for the maximum fill time, the controller will stop all action and wait 20 minutes to re-try water fill. During this time the Check Water light on the control panel will be blinking,

Maximum Freeze Time. If the freeze cycle should extend to 60 minutes, the controller will automatically put the machine into a Harvest cycle.

Maximum Harvest Time. 6 minutes

Time between restarts. After the machine has operated and then turned off, the controller will not restart the machine for four minutes.