Scotsman Ice SCCG50, SCCP50 service manual Refrigeration Service

Models: SCCP50 SCCG50

1 32
Download 32 pages 60.01 Kb
Page 32
Image 32
Refrigeration Service

SCCG50 & SCCP50

Service Manual

Refrigeration Service

This ice machine use R-134a type refrigerant. There are specific rules for handling that refrigerant.

To check for system pressures, add a field supplied clamp-on type service valve as a temporary means of system access. After diagnosis and before final repair, replace the clamp-on type valve with valves that are brazed onto the process tubes of the system.

Use a low flow of dry nitrogen when brazing on the system.

Install a new filter drier when replacing a refrigeration component or after a refrigerant leak repair.

Evacuate the system to at least 300 microns and use a micron gauge to measure the evacuation level.

Weigh in the nameplate charge. The machine is critically charged and a partial ounce mis-charge will affect performance.

June 2008

Page 32

Page 32
Image 32
Scotsman Ice SCCG50, SCCP50 service manual Refrigeration Service