3.DoNOTterminate over public walkways. Avoid areas

where condensate may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.

4.The vent termination shall be located at least 4'horizontally from any electric meter, gas meter, regulator, and any relief equipment. These distances apply ONLY to U.S. installa- tions.

The vent termination is to be located at least 3' above any forced air inlet located within 10' ; and at least 10' from a combustion air intake of another appliance, except another direct vent furnace intake.

In Canada, the Canadian Fuel Gas Code takes prece- dence over the preceding termination instructions.

Vent Termination Clearances

(United States Only)

In Canada See Canadian Fuel Gas Code

OtherThan

OtherThan

DirectVent

Terminal

\

Condensate Drain Trap

This furnace removes both sensible and latent heat from the prod-

ucts of combustion. Removal of the latent heat results in con-

densation of the water vapor. The condensate is removed from the furnace through the drains in the plastic transition and the vent fitting. The drains connect to the externally mounted condensate drain trap on the left or right side of the furnace.

The startup of a new furnace will involve a cycle or two of the fur- nace to properly prime the condensate trap with water. Until the trap is fully primed, some condensate will be pulled into the com- bustion blower. The furnace may cycle on the pressure switch connected to the plastic transition box due to condensate buildup.

After the trap is primed, the condensate will start draining from the furnace. The combustion blower will clear out any remaining con- densate in the blower housing through the vent fitting down- stream of the blower. Note that the condensate trap can also be primed by pouring water into the vent drain side of the trap. Re- move the small plastic ca p and clamps from the unused drain stu b on the vent drain side of the condensate trap. Connect a section of the 518" OD hose with a funnel to the drain stub and pour eight (8) ounces of water into the trap. Remove the hose and replace the

plastic cap and clamp. This will prime both the vent and the transi- tion sides of the trap.

The condensate drain trap supplied with the furnace MUST be used. The drain connection on the condensate drain trap is sized for 3/4" PVC or CPVC pipe, however alternate 1/2" CPVC (nomi- nal 5/8" O.D.) or vinyl tubing with a minimum inner diameter (I.D.) of 5/8" may also be used, as allowed by local codes. Alternate drain pipes and hoses may be used as allowed by local codes.

The drain line must maintain a 1/4" per foot downward slope to-

ward the drain. 1/4" per foot is recommended. Installation of an

overflow line is recommended when the 1/4" per foot slope to the condensate drain cannot be maintained. See Figure 1 for proper routing and installation of the overflow.

DO NOT trap the drain line in any other location than at the con- densate drain trap supplied with the furnace.

FROZEN AND BURST WATER PIPE HAZARD

If a condensate pump is installed, a plugged condensate drain or a failed pump may cause the furnace to shut

down. Do not leave the home unattended during freezing

weather without turning off water supply and draining

water pipes or otherwise protecting against the risk of frozen pipes.

Failure to do so may result in burst water pipes, serious

property damage and/or personal injury.

If possible DO NOT route the drain line where it may freeze. The drain line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.

1.A condensate sump pump MUST be used if required by lo- cal codes, or if no indoor floor drain is available. The con-

densate pump must be approved for use with acidic condensate.

A plugged condensate drain line or a failed condensate

pump will allow condensate to spill. If the furnace is installed where a condensate spill could cause damage, it

is recommended that an auxiliary safety switch be installed to prevent operation of the equipment in the event of pump failure or plugged drain line. If used, an auxiliary safety

switch should be installed in the R circuit (low voltage) ONLY.

3.If the auxiliary switch in the condensate pump is used, the furnace may shut down due to a blocked condensate line or failed pump. To prevent frozen water pipes see the "Frozen Water Pipe Hazard" section on Page 4 of this manual.

Condensate Drain Trap Freeze Protection

Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper op-

eration or damage to the equipment. If the the furnace environ- ment has the potential of freezing, the drain trap and drain line must be protected. Use 3 to 6 watt per foot at 115 volt, 40 ° F self- regulating shielded and waterproof heat tape. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow

the heat tape manufacturer's recommendations.

44001 111400

[_

Page 13
Image 13
Sears N9MP1 Condensate Drain Trap Freeze Protection, United States Only, Canada See Canadian Fuel Gas Code OtherThan

9MPD, N9MP1, N9MP2 specifications

The Sears N9MP2, N9MP1, and 9MPD are prominent models in the realm of residential heating systems, specifically designed to provide efficient and effective heating solutions. These models are part of Sears' commitment to quality and innovation, making them a popular choice among homeowners seeking reliability and performance.

The N9MP2 is a high-efficiency multi-speed gas furnace that boasts an impressive AFUE (Annual Fuel Utilization Efficiency) rating. This feature allows the furnace to convert a significant portion of fuel into usable heat, which effectively translates to lower energy bills for homeowners. The unit is equipped with a two-stage gas valve that provides increased comfort by adjusting the heating output based on demand, ensuring an even temperature throughout the home.

The N9MP1, like its counterpart, is known for its reliability and efficiency. It offers a single-stage operation that is ideal for homes needing consistent heating without the necessity for the more complex stages present in two-stage systems. This model also has a good AFUE rating, making it a cost-effective solution for families looking to reduce their heating expenses. Its design is tailored for easy installation and maintenance, allowing homeowners to keep their heating systems running at optimal performance without hassle.

The 9MPD model takes a step further with its advanced technology integration. It features a sophisticated control board that allows for easier diagnostics and enhanced system management. The 9MPD is also designed with quiet operation in mind, employing advanced sound-reduction technologies to minimize noise levels during heating cycles. Homeowners will appreciate the peace and quiet it brings, particularly in shared living spaces.

All three models are equipped with high-quality insulation and specialized heat exchangers that enhance their thermal efficiency. Additionally, they are designed with safety features such as automatic shut-off systems and robust flame rollout protection, ensuring a safe heating experience.

In terms of characteristics, these models are generally constructed with durable materials, designed to endure harsh weather conditions while providing consistent heating. They can be connected to various home automation systems, which adds to their appeal for tech-savvy consumers.

In conclusion, the Sears N9MP2, N9MP1, and 9MPD represent a comprehensive lineup of reliable, efficient, and technologically advanced heating systems suitable for contemporary homes. Their dedication to performance ensures that homeowners enjoy a warm and energy-efficient environment throughout the chilly seasons.