Sears 9MPD, N9MP2, N9MP1 Natural Gas Input Rating Check, Typical Gas Piping for Upflow, Example

Models: 9MPD N9MP1 N9MP2

1 62
Download 62 pages 59.01 Kb
Page 32
Image 32

Typical Gas Piping for Upflow

Drip Leg and Union, Union* should be outside the

Gas

(Single Pipe)

cabinet. Manual shut-off valve MUST he upstream of

 

 

dripleg, union,

Manual shut- off

 

 

 

valve

 

 

Useelbows and3" pipenippleto connectvalveto pipingwhen usingright side gas pipe entry.

LP Lowpressure

switch. Optional on some models.

nipp

25-23-37b

* Union may be installed inside the cabinet when necessary because

Typical Gas Piping for Downflow

Use elbows and 3" pipe nipple to connect valve's- to piping when using left side gas pipe entry.

 

 

 

 

 

 

 

 

 

Manual shut- off

 

 

 

 

 

LP

Low

pressure

valve

 

 

 

 

 

 

 

 

 

 

 

switch.

Optional

LP

 

 

 

 

 

 

conversion.

 

 

 

 

 

Drip Leg and Union, Union* should

 

 

 

 

the

cabinet.

Manual

shut-off

valve MUST

be

 

 

 

upstream

of dripleg,

union,

and furnace.

 

 

 

 

 

 

 

 

 

Gas

Pipe Grommet

*Union

may

be installed

inside the

cabinet

when

necessary

(Single Pipe)

because

of

clearances.

 

 

 

 

 

 

25-23-39

 

 

 

 

 

 

 

 

 

Natural Gas Input Rating Check

Example

 

 

Natural Gas

No. of Seconds

Time Per Cubic

BTUPer

NOTE: The gas meter can be used to measure input to furnace.

 

 

 

 

Rating is based on a natural gas BTU content of 1,000 BTU's per

PerHour3,600

_

Foot in48Seconds

75,000Hour

BTU1,000Content

cubic meter. Check with gas supplier for actual BTU content.

 

 

 

 

1.Make sure burner compartment door is in place before per- forming the following steps.

2.Turn OFF gas supply to all appliances and start furnace.

1,000 x 3,600 + 48 = 75,000 BTUH

3.Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution. Refer to Ex- ample.

[_

440 01 111400

Page 32
Image 32