Horizontal Furnace Installation

This furnace can be installed horizontally in an attic, basement, crawl space, alcove, or suspended from a ceiling in a basement or utility room. See Figure 4. Do not install furnace on its back or in

the reverse airflow positions as safety control operation will be ad- versely affected.

_

_!'i [ Typical

Horizontal

Installation

Inlet Pipe (not used on Single Pipe model)

Vent

C_

Condensate

Trap

25-23-34

NOTE: 6" bottom clearancerequired for condensatetrap.

3. Combustion & Ventilation Air

For Single Pipe Installation

If the furnace is to be suspended from the floor joists in a crawl space or the rafters in an attic, it is necessary to use steel pipe straps or an angle iron frame to rigidly attach the furnace to pre- vent movement. These straps should be attached to the furnace with sheet metal screws and to the rafters or joists with bolts. The preferred method is to use an angle iron frame bolted to the rafters or joists. (Take caution to allow door panels to be removed for maintenance)

If the furnace is to be installed in a crawl space, consult local

codes. A suitable concrete pad or blocks are recommended for crawl space installation on the ground.

NOTE: 6" bottom clearance required for condensate trap.

Thirty (30) inches between the front of the furnace and adjacent construction or other appliances MUST be maintained for service clearance.

Keep all insulating materials clear from Iouvered door. Insulating materials may be combustible.

The horizontal furnaces may be installed directly on combustible wood flooring or supports as long as all required furnace clear- ances are met. See Figure 4.

This furnace MUST NOT be installed directly on carpeting or tile

or other combustible material other than wood flooring or sup- ports.

For horizontal installation over a finished living space. A field fab- ricated auxiliary drain pan with drain pipe is required to prevent damage by overflow due to blocked condensate drain.

2.Connect ducts or openings directly to outside.

3.When screens are used to cover openings, they MUST be no less than 1/4" mesh.

CARBON MONOXIDE POISONING HAZARD

Failure to provide adequate combustion and ventilation

air can result in death and/or personal injury.

Use methods described here to provide combustion and

ventilation air.

Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open-

ings for supplying combustion and ventilation air must comply

with National Fuel Gas Code, NFPA54/ANSI Z223.1, 2001 (or current edition) and applicable provisions of local building codes.

This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a fac- tory-built or masonry chimney. If this furnace is replacing a pre-

viously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for

the other remaining appliance(s). See "Venting and Combustion Air Check"in this section, This furnace MUST be vented to the

outside.

Air Openings and ConnectingDucts

1.Total input rating for all non direct vent gas appliances MUST be considered when determining free area of open- ings.

4.The minimum dimension of rectangular air ducts MUST NOT be less than 3".

5.When sizing grille or louver, use the free area of opening. If

free area is NOT stamped or marked on grill or louver, as- sume a 20% free area for wood and 60% for metal.

Confined Space Installation

NOTE: A confined space is defined as an area with less than 50 cubic feet per 1,000 BTUH input rating for all gas appliances installed in the area.

Requirements

Provide confined space with sufficient air for proper com- bustion and ventilation of flue gases using horizontal or ver- tical ducts or openings.

Figure 5 illustrate how to provide combustion and ventila- tion air. A minimum of two permanent openings, one inlet and one outlet, are required.

One opening MUST be within 12" of the floor and the se- cond opening within 12" of the ceiling.

E_

44001 111400

Page 8
Image 8
Sears 9MPD Combustion & Ventilation Air For Single Pipe Installation, Air Openings and ConnectingDucts, Condensate Trap

9MPD, N9MP1, N9MP2 specifications

The Sears N9MP2, N9MP1, and 9MPD are prominent models in the realm of residential heating systems, specifically designed to provide efficient and effective heating solutions. These models are part of Sears' commitment to quality and innovation, making them a popular choice among homeowners seeking reliability and performance.

The N9MP2 is a high-efficiency multi-speed gas furnace that boasts an impressive AFUE (Annual Fuel Utilization Efficiency) rating. This feature allows the furnace to convert a significant portion of fuel into usable heat, which effectively translates to lower energy bills for homeowners. The unit is equipped with a two-stage gas valve that provides increased comfort by adjusting the heating output based on demand, ensuring an even temperature throughout the home.

The N9MP1, like its counterpart, is known for its reliability and efficiency. It offers a single-stage operation that is ideal for homes needing consistent heating without the necessity for the more complex stages present in two-stage systems. This model also has a good AFUE rating, making it a cost-effective solution for families looking to reduce their heating expenses. Its design is tailored for easy installation and maintenance, allowing homeowners to keep their heating systems running at optimal performance without hassle.

The 9MPD model takes a step further with its advanced technology integration. It features a sophisticated control board that allows for easier diagnostics and enhanced system management. The 9MPD is also designed with quiet operation in mind, employing advanced sound-reduction technologies to minimize noise levels during heating cycles. Homeowners will appreciate the peace and quiet it brings, particularly in shared living spaces.

All three models are equipped with high-quality insulation and specialized heat exchangers that enhance their thermal efficiency. Additionally, they are designed with safety features such as automatic shut-off systems and robust flame rollout protection, ensuring a safe heating experience.

In terms of characteristics, these models are generally constructed with durable materials, designed to endure harsh weather conditions while providing consistent heating. They can be connected to various home automation systems, which adds to their appeal for tech-savvy consumers.

In conclusion, the Sears N9MP2, N9MP1, and 9MPD represent a comprehensive lineup of reliable, efficient, and technologically advanced heating systems suitable for contemporary homes. Their dedication to performance ensures that homeowners enjoy a warm and energy-efficient environment throughout the chilly seasons.